Overcurrent
Fuses
Circuit Breakers
Short-Circuit Current
Protection Devices
100
  • 100: Overcurrent is current in excess of the equipment ampere rating or ampacity of the wires. It may result from a(an) _.


    • a. overload

    • b. short circuit

    • c. ground fault

    • d. any of these

d. any of these

100
  • 100: Fuses consist of a _ element connected to end blades or caps, surrounded by silica sand filler material enclosed in a tube.


    • a. conductive

    • b. foam

    • c. light

    • d. nonconductive

a. conductive

100
  • 100: _ circuit breakers operate on the principle that as the current increases, the time it takes for the device to open decreases.


    • a. Inverse time

    • b. Adjustable trip

    • c. Instantaneous trip

    • d. all of these

  • a. Inverse time

100
  • 100: What is the approximate available short-circuit current on the secondary of a 50 kVA, 480V to 240V single-phase transformer having an impedance rating of 1.20 percent?


    • a. 10,000A

    • b. 12,000A

    • c. 14,000A

    • d. 17,000A

d. 17,000A

100
  • 100: Equipment must have a(an) _ current rating that permits the protection device to clear a short circuit or ground fault without extensive damage to the equipment components.


    • a. overload

    • b. short-circuit

    • c. ground-fault

    • d. none of these

b. short-circuit

200
  • 200: A(An) _ is the operation of equipment or wires in excess of their rated ampacity.


    • a. overload

    • b. short circuit

    • c. ground fault

    • d. all of these

a. overload

200
  • 200: When a sustained overload occurs through the element(s) of a fuse, the heat melts _, stopping the flow of current.


    • a. several elements

    • b. all of the elements

    • c. a portion of the element

    • d. none of these

c. a portion of the element

200
  • 200: The _ trip element of a circuit breaker operates on the time-current principle of being inversely proportional to the magnitude of the current.


    • a. magnetic

    • b. electronic

    • c. thermal

    • d. none of these

c. thermal

200
  • 200: The factor(s) that impact the available short-circuit current on the load side of a transformer is(are) _.


    • a. system voltage

    • b. kVA rating

    • c. impedance

    • d. all of these

d. all of these

200
  • 200: If the protective device is not rated to _ the available fault current at its listed voltage rating, it can explode while attempting to clear the fault.


    • a. interrupt

    • b. withstand

    • c. hold

    • d. break

a. interrupt

300
  • 300: A(An) _ occurs when an unintentional electrical connection occurs between a phase wire and metal parts of enclosures, raceways, and/or equipment.


    • a. overload

    • b. short circuit

    • c. ground fault

    • d. all of these

c. ground fault

300
  • 300: A _ fuse is referred to as a nontime-delay fuse and is the least expensive type.


    • a. single-element

    • b. dual-element

    • c. current-limiting

    • d. all of these

a. single-element

300
  • 300: Inverse time circuit breakers have a(an) _ trip unit that responds to short-circuit and ground-fault currents.


    • a. adjustable

    • b. instantaneous

    • c. electromagnetic

    • d. none of these

c. electromagnetic

300
  • 300: The available short-circuit current is different at each point of the electrical system; it is highest at the _.


    • a. branch circuit

    • b. feeder

    • c. service

    • d. utility transformer

d. utility transformer

300
  • 300: Selective coordination of overcurrent protective devices prevents _ power losses to loads not part of the faulted circuit.


    • a. intended

    • b. unintended

    • c. excessive

    • d. none of these

b. unintended

400
  • 400: The available short-circuit current is highest at the utility transformer and lowest at the _ load because of the impedance of the circuit.


    • a. branch-circuit

    • b. feeder

    • c. service

    • d. utility transformer

400: a. branch-circuit

400
  • 400: A _ fuse is designed to clear a short circuit or ground fault in less than one-half a cycle.


    • a. one-time fuses

    • b. dual-element fuses

    • c. special trip fuses

    • d. current-limiting

d. current-limiting

400
  • 400: _ circuit breakers permit the thermal and electromagnetic trip current and/or time settings to be adjusted to provide the user with flexibility for specific applications.


    • a. Inverse time

    • b. Adjustable trip

    • c. Instantaneous trip

    • d. all of these

b. Adjustable trip

400
  • 400: The available short-circuit current at the _ transformer is provided by the electric utility; no calculation is required.


    • a. occupancy

    • b. building

    • c. premises

    • d. utility

d. utility

400
  • 400: Lack of selective coordination of overcurrent protective devices can result in unintended _ to loads not part of the faulted circuit.


    • a. surges

    • b. power losses

    • c. blackouts

    • d. shutdowns

b. power losses

500
  • 500: To quickly clear a(an) _, the ground-fault current needs to rise to a level between ten and twenty times the rating of the circuit overcurrent protective device.


    • a. overload

    • b. arcing fault

    • c. ground fault

    • d. none of these

c. ground fault

500
  • 500: When a short circuit or ground fault occurs through the element of a fuse, the heat in the element rises to a point where _ in the fuse melt to stop electrical current flow.


    • a. multiple conductive segments

    • b. a small portion of the segment

    • c. all of the segments

    • d. none of these

a. multiple conductive segments

500
  • 500: Circuit breakers and fuses are intended to interrupt the circuit, and they must have an ampere interrupting rating (AIR) _ for the available short-circuit current.


    • a. inadequate

    • b. sufficient

    • c. sustainable

    • d. none of these

b. sufficient

500
  • 500: As the overload current _, the time it takes for the thermal trip element to open decreases.


    • a. increases

    • b. decreases

    • c. remains the same

    • d. none of these

a. increases

500
  • 500: _ of overcurrent protective devices is when the devices are designed to clear a short circuit or ground fault in a manner that localizes the short circuit or ground fault to that given circuit.


    • a. Plotting

    • b. Sequencing

    • c. Selective coordination

    • d. none of these

c. Selective coordination