WHAT IS THE TAKE UP FOR 3/4 EMT?
6"
MINIMUM SUPPORT DISTANCE FOR 3/4" EMT
3' FROM BOX AND EVERY 10'
WHEN WIRING A OVERLOAD FOR MOTOR PROTECTION DO YOU USE N/O OR N/C CONTACTS
N/C
HOW MANY CCC CAN YOU INSTALL IN A CONDUIT BEFORE YOU HAVE TO DERATE THEM?
3
WHEN LOOKING FOR EXACT LOCATIONS ON LIGHTS WHAT PRINT WOULD YOU USE?
REFLECTED CEILING PRINT
WHAT IS THE TAKE UP FOR 1" EMT?
8"
SUPPORT DISTANCE FOR FLEXIBLE METALIC CONDUIT
12" FROM BOX AND EVERY 4 1/2 FEET
IS THE STOP BUTTON N/O OR N/C
N/C
ALLOWABLE VOLTAGE DROP FOR BRANCH CIRCUITS?
3%
WHEN LOOKING FOR EXACT LIGHT POLE BASE PATTERNS WHERE WOULD YOU LOOK?
EITHER SUBMITTALS OR DETAILS
WHAT IS THE SHRINK FOR A 22.5 DEG BEND
3/16"
SUPPRT DISTANCE FOR 12-2 MC CABLE
12" FROM BOX AND EVERY 6'
WHAT ARE NORMALLY OPEN CONTACTS 2 AND 3 SPECIFICALLY FOR ON A MOTOR STARTER?
3 WIRE HOLDING CKT
OVER WHAT SIZE CONDUIT NIPPLE DO YOU HAVE TO START DERATING CONDUCTORS
OVER 24"
WHY SHOULD YOU ALWAYS CHECK THE REVISION DATE ON BLUEPRINTS?
AS REVISIONS ARE MADE YOU NEED THE MOST UP TO DATE VERSION
WHAT IS THE SHRINK FOR A 45 DEGREE BEND
3/8"
SUPPORT DISTANCE ON ELECTRICAL NON METALLIC TUBING (ENT)
3' FROM BOX AND EVERY 3'
WHAT ARE TERMINATIONS A1 AND A2 ?
COIL TERMINATIONS
WHAT IS YOUR ALLOWABLE PERCENTAGE FILL FOR A 24" NIPPLE WITH CONDUCTORS?
60%
FIRST PLACE TO LOOK FOR WHO SUPPLIES HVAC DISCO,VFD,STARTER
MECANICAL EQUIPMENT SCHEDULE
TAKEUP FOR 1 1/4" EMT
11"
SUPPORT DISTANCE FOR MI CABLE
EVERY 6'
ON A 8 PIN RELAY WHICH 2 PINS ARE YOUR COIL?
7 AND 2
ALLOWABLE VOLTAGE DROP FOR FEEDERS?
5%
WHAT IS REDLINING ON A PRINT?
REDLINING THE CHANGES MADE DURING INSTALL FOR THE CUSTOMER TO REFERANCE