100

The voltage produced by a generator is zero for some period of time for the   ?  -phase power system. The voltage falls to zero   ?  each cycle.

Single and Twice

100

the line voltage is higher than the phase voltage by a factor of 1.73 on what connection

(Wye) also The system has a common connection for all three windings.

The line current is equal to the phase current.

100

If phase (A) has 120v and 35A ON A Delta xfmr what is line current

60.55 or 61 

(I)line = (I)winding x 1.73

100

Which winding on a generator induces voltage?

Armature

100

generator are devices that turn _ energy into _ energy

mechanical and electrical

200

A single coil generator spinning in a magnetic field will produce a full sine wave for every   ?   of rotation.


360 degrees

200

An amusement park has a delta connected , 3 phase , 480 volt service with a balance load of 224A and a power factor of 86%. How much power in Kw is being consumed?

3 phase kw= (E line * I line * 1.73 * Pf) / 1000


159.96 kw 

160 kw

200

What are the two basic styles of generators?

revolving armature and revolving field

200

what is one half cycle of a sine wave called

Alternation

test instruments

200

Any time a three-phase current unbalance exceeds   ?  %, electricians must test for voltage unbalance.

10

test instruments

300

what controls the number of times the solid-state switches in the inverter section of a Pulse Width Modulated (PWM) variable frequency drive turn on and turn off per second?

Carrier Frequency

300

A 4-pole generator will be supplying several loads that are designed for 84 hertz. At what speed does the generator need to be driven?

S(speed)= (120*F)/ # OF POLES

2520 RPM

300

What are the three factors that determine the output of a generator

The number of turns in the armature

The strength of the magnetic field

The speed of the armature

300

What is the time displacement between voltages on a 3-phase generator if the frequency is 72 hertz?

time period= 1/f

time vd(voltage drop)= time period/ # of phases

4.63 ms

.004629

300

The source for mechanical motion supplied to a generator is referred to as the   ?  .

prime mover

400

if a 3-phase resistive load is connected to the generator, what is the total power supplied?

240V 20A Delta

(POWER)three phase = (E)line x (I)line x 1.73

8304

400

how many poles are required for a generator that is 60hz at 3250 rpm

P= (f*120)/S


2.215 p

2 poles

400

what are the two types of rotating field construction generators

SALIENT POLE ROTOR and ROUND ROTOR

salient poles are pole face that are very pronounced and jut out

round rotor uses a smooth, longer, and narrower construction to minimize wind resistance and centrifugal forces

400

When is an armature called a stator

When the revolving field AC generator has its armature windings positioned around the generator housing.

or when the armature is stationary

400

If the only criterion for power factor correction were to reduce the utility bill, the capacitors would most likely be connected at the main service in order to achieve a lower priced installation.

true or false

True

500

which two ways can a transistor be used

amplifier and switch

500

what does the decibel scale on a multimeter indicate

the comparison between two or more signal powers or voltages.

500

a rotating exciter that is on the same shaft as the main generator is called a?

brushless exciter

exciters are made stationary or rotating

500

what are the three types of armature windings found in generators

1. frog leg ; are middle of the road type windings. most common configuration, moderates voltage and current found in large dc equipment

2. Lap wound ; designed for high voltage low current usually larger wire

3. Wave wound ; designed for high current low voltage usually smaller wire

500

A 3/0 AWG copper feeder conductor is tapped with 20 feet of 2 AWG conductor. What is the maximum OCPD size allowed at the termination of the tap conductors installed in a fused switch or circuit breaker? (All conductors and terminations are rated 75°C.)

110A

240.6(A)

TABLE 310.16

240.21(B)

240.4(B)