Description of Hazard

100

Wire rope guardrail system had a top rail that deflected to 37" high

Per standard 1926 502 b 4, shall not deflect less than 39". 

Abatement: Tighten to meet 200# minimum

200

Gasoline and diesel fuel were stored in containers that were not marked or labeled. 

Per 1926.59 f6, workplaces should do labeling. 

Abatement: Properly label all containers with Product identifier

300

Temporary electrical outlets were not GFCI protected on a Non-Assured Equipment Grounding Conductor Program job site. 

Per 1926.404 b 1 ii   Install GFCI's

Abatement: Install GFCI's 

400

Employer did not ensure that a competent person was designated and had completed  regular and frequent inspections of the job site, materials and equipment.

Per 1926 20 b 2 Comp Person should provide regular inspections of job sites etc. 

Abatement: Competent Person required to do daily inspections.

500

Eye of wire rope sling was formed using wire rope clips

Per 1926 251 c 4 iii, Eyes in wire rope slings shall not be formed by wire rope clips

Abatement: Eyes should be formed using eye splices or swaged eyes