Pools
OverCurrent Protection
Boxes
Clearances
Services
100




Low voltage lighting systems for Pools, Spas, Fountains and similar locations must not be installed less than ____ from the edge of the water:

what is 10 ft

100




Overcurrent devices located next to the equipment can be mounted above ______, if accessible by portable means:

what is 6'7

100






The distance from the raceway entry of the box or conduit body to the opposite wall must not be less than _____ times the trade size of the largest raceway, plus the sum of the trade sizes of the remaining raceways on the same wall and row:

what is 6

100





The minimum acceptable space width of working space is ______:

what is 30 in



110.26(A)(1)

100




The underground conductors that connects between the utility electric supply and the service point is ______

what is a service lateral



Article 100 

200





If space limitations prevent ____ of space from the pool, underground wiring must be installed in a complete raceway system:

what is 5ft

200





Plug fuses are permitted to be used only when the circuit voltage does not exceed _____ between conductors:

What is 125v

200






Boxes and conduit bodies containing conductors _____ and larger that are required to be insulated must be sized so the conductor insulation will not be damaged:

what is 4 AWG

200





For equipment rated 800 A or more, personal doors located less than _____ from the nearest edge of the working space must open in the direction of egress and have listed panic hardware:

what is 25 ft



110.26(C)(3)

200





Vertical clearance of overhead service conductors  ______ shall be maintained over public streets, alleys and parking areas subjected to truck traffic:

what is 18ft



230.24(B)(4)

300





At least one 15A or 20A, 125V receptacle must be located at least ____ from the inside wall of the spa or hot tub.

what is 6 ft

300




Feeder tap conductors in a circuit up to _______ long are permitted without overcurrent protection at the tap location:

what is 10 ft

300





Where the box opening is less than 8 in., length of free conductors must extend atleast _____ outside the box opening:

what is 3 in


300.14

300





If the raceways enter a switchboard, switchgear, floor-standing panelboards or similar enclosure, the raceways, including end fittings must nor rise more than _____ above the bottom of the enclosure:

what is 3 in



408.5

300





The point of connection between serving utility and the premises wiring:

what is service point



Article 100

400





The parts of a permanently installed pool, outdoor spa, or outdoor hot tub must be bonded together with a solid copper conductor not smaller than _____ with listed pressure connectors

what is 8 AWG

400





Edison base fuses are classified to operate at not more than 125V and have an ampere rating of not more than ______:

what is 30 A

400





A single volume allowance for one or more equipment grounding conductors enter a box having largest equipment grounding conductor of size 18 AWG is _______:

what is 1.5in3



Table 314.16(B)

400





The minimum acceptable space width of working space is ______:


what is 30 in




110.26

400





______ circuit breakers or sets of fuses are acceptable as over current device to provide overload protection in one family dwellings

2 to 6



230.71(B)

500






For fixed or stationary equipment other than an underwater luminaire for permanently installed pools , cord must have a copper equipment grounding conductor not smaller than _____ and the cord must terminate at a grounding type attachment plug:

what is 12 awg

500





The overcurrent protection device of non-motor appliances must not exceed ________ if the overcurrent device rating is not marked:

what is 20 A

500





The minimum distance from where the conductors enter the box or conduit body to the opposite wall must not be less than ____ times the trade size of the largest raceway:

what is 8



314.28(A)(1)

500





Underground service conductors must be smaller than ______ copper conductor:

what is 8 AWG



230.31(B)