Low voltage lighting systems for Pools, Spas, Fountains and similar locations must not be installed less than ____ from the edge of the water:
what is 10 ft
Overcurrent devices located next to the equipment can be mounted above ______, if accessible by portable means:
what is 6'7
The distance from the raceway entry of the box or conduit body to the opposite wall must not be less than _____ times the trade size of the largest raceway, plus the sum of the trade sizes of the remaining raceways on the same wall and row:
what is 6
The minimum acceptable space width of working space is ______:
what is 30 in
110.26(A)(1)
The underground conductors that connects between the utility electric supply and the service point is ______
what is a service lateral
Article 100
If space limitations prevent ____ of space from the pool, underground wiring must be installed in a complete raceway system:
what is 5ft
Plug fuses are permitted to be used only when the circuit voltage does not exceed _____ between conductors:
What is 125v
Boxes and conduit bodies containing conductors _____ and larger that are required to be insulated must be sized so the conductor insulation will not be damaged:
what is 4 AWG
For equipment rated 800 A or more, personal doors located less than _____ from the nearest edge of the working space must open in the direction of egress and have listed panic hardware:
what is 25 ft
110.26(C)(3)
Vertical clearance of overhead service conductors ______ shall be maintained over public streets, alleys and parking areas subjected to truck traffic:
what is 18ft
230.24(B)(4)
At least one 15A or 20A, 125V receptacle must be located at least ____ from the inside wall of the spa or hot tub.
what is 6 ft
Feeder tap conductors in a circuit up to _______ long are permitted without overcurrent protection at the tap location:
what is 10 ft
Where the box opening is less than 8 in., length of free conductors must extend atleast _____ outside the box opening:
what is 3 in
300.14
If the raceways enter a switchboard, switchgear, floor-standing panelboards or similar enclosure, the raceways, including end fittings must nor rise more than _____ above the bottom of the enclosure:
what is 3 in
408.5
The point of connection between serving utility and the premises wiring:
what is service point
Article 100
The parts of a permanently installed pool, outdoor spa, or outdoor hot tub must be bonded together with a solid copper conductor not smaller than _____ with listed pressure connectors
what is 8 AWG
Edison base fuses are classified to operate at not more than 125V and have an ampere rating of not more than ______:
what is 30 A
A single volume allowance for one or more equipment grounding conductors enter a box having largest equipment grounding conductor of size 18 AWG is _______:
what is 1.5in3
Table 314.16(B)
The minimum acceptable space width of working space is ______:
what is 30 in
110.26
______ circuit breakers or sets of fuses are acceptable as over current device to provide overload protection in one family dwellings
2 to 6
230.71(B)
For fixed or stationary equipment other than an underwater luminaire for permanently installed pools , cord must have a copper equipment grounding conductor not smaller than _____ and the cord must terminate at a grounding type attachment plug:
what is 12 awg
The overcurrent protection device of non-motor appliances must not exceed ________ if the overcurrent device rating is not marked:
what is 20 A
The minimum distance from where the conductors enter the box or conduit body to the opposite wall must not be less than ____ times the trade size of the largest raceway:
what is 8
314.28(A)(1)
Underground service conductors must be smaller than ______ copper conductor:
what is 8 AWG
230.31(B)