100

Class A GFCI devices are designed to trip at 6mA or more

What is Yes - Definitions - page 63

100

What is the smallest copper AWG conductor size than can be used for branch circuit?

What is #14 AWG - Rule 4-002

100

What is the minimum wire size allowed by the code for consumer service conductors?

What is #10 Copper and #8 Aluminum - Rule 6-302-4

100

A single family dwelling has a main service of 100 amps. What is the minimum space requirement for the branch circuit breakers (or fuses) in the panelboard?

What is "as required plus 4 free spaces, with room for 1 two-pole breaker" Rule 8-108 (1)

100

Is it required by the code to ground the neutral conductor of a three-wire, AC system?

What is Yes 

Rule 10-208 (1) (b)

100

What is the minimum wire size of power conductors that may be run in parallel?

What is #1/0 AWG

Rule 12-108-1

100

Overload relay heaters may be connected ahead of the power contacts in a magnetic starter.

What is False (No) 

Rule 14-404

200

What must be done when a firewall is pierced by an electrical cable or raceway?

What is Sealed - 2-128-2

200

A cable or raceway contains 3 of #6 R90 copper branch circuit conductors. What is the maximum current each can carry according to the code? Equipment is rated for 75 degree temperature terminations

What is 65 Amps - Rule 4-004 (1) (b) and Table 2 

200

What is the definition of a "Service Box"?

What is an "assembly consisting of an enclosure that can be locked or sealed, containing either fuses and a switch or a circuit breaker, and of such design that it is possible to operate the switch of circuit breaker to an open position by manual means when the box is closed  

Rule - definitions page 69

200

What is the voltage divisor, according to the code, for a three-wire 120/208 volt system consisting of two ungrounded lines and the neutral, for the purpose of calculating current demands from wattages or volt-amperes?

What is 208V Rule 8-100

200

Are bonding jumpers required on expansion joints for rigid steel conduit to assure a continuous electrical bond?

What is Yes 

Rule 10-608 or 12-1012-2

200

How far away must N.M.S.C. be installed from outer edges or surface of studs, joist, or similar wooded members through which it may run?

What is 32mm 

Rule 12-516-1

200

Standard fuses may be used for protection of Hot Water tanks

What is No

Rule 14-610

300

What is the maximum branch circuit voltage-to-ground for a single dwelling?

What is 150V to Ground - Rule 2-110

300

According to the code, is it mandatory that lamp holders, receptacles, etc. are connected in such a way so as not to interrupt the identified conductor of the circuit if these devices were to be replaced?

What is Yes - Rule 4-030-4

300

What is the minimum length that service conductors must extend beyond the supply end of the consumer service head? (Drip loops)

What is 750 mm - Rule 6-302-3

300

How would you determine the feeder conductor’s ampacity which supply loads of a cyclic nature? The various loads cycle in such a way that the maximum load will never be supplied by the feeder conductors at any time.

What is The maximum at any one-time Rule 8-106 (4)

300

Is an extra bonding conductor required when rigid metal conduit is buried underground?

What is Yes 

Rule 10-610-1-a-iii

300

A three-conductor 600 volt TECK cable is to be direct buried in a trench dug across a narrow street, to be used as feeder conductor for an expanding tailor shop. Give the minimum depth requirements for the trench and the installation of the cable according to the code.

600 mm with no mechanical protection

450 mm with mechanical protection

(sand above and below)

warning tape half way from cable to the surface 

12-012 (1) (4) (11) and Table 53

300

A 15 amp receptacle may be connected to a 20 amp breaker provided the conductor ampacity is 20 amp minimum.

What is NO

Rule 14-600

400

What kind of enclosure would you choose for an installation in a car wash where the electrical equipment may be subject to direct streams of water?

What is Type 4 - Rule 2-400 (1) (d) 

400

Eight aluminum branch circuit conductors are installed in a single raceway, 3 of which are neutral conductors (carrying only the unbalanced current). What is the ampacity correction factor of each conductor?

What is 80% - Rule 4-004 (2) (c) and (3) and Tables 5C and 4

                                                                    

400

Can a meter be installed in a 200 amp, 480 Volt service without a disconnect preceding it?

What is NO (limited to 300V line to line) - Rule 6-402 (2) (b)

400

You use your voltmeter to find that the voltage at the load is 112.8V, the source voltage measured at on the utility side of the service is 120V.  Does this meet the requirement of the CEC?

What is No (this is a 7.2% voltage drop, we are only allowed 5% from the utility side of the service to the load) 

Rule 8-102 (1) (b)

400

A six metres run of service conduit is installed in such a way that it cannot be reached from the ground nor is it in contact with any conductive surface. Must this conduit be bonded to ground?

What is Yes, it is a service so bonding is required 

Rule 10-604 (1) 

400

How many #14AWG conductors can be installed in a 3 x 2 x 1 1/2 Device Box 

What is 5 

Rule 12-3034 and Table 23 

400

A 250 amp fuse may be used to protect a feeder to an installation with a demand load of 228 amps (non continuous.)


What is Yes

Rule 14-104 (a) and Table 13

500

In an apartment building what are the requirements in order to install a 347V fixed mounted heater (with a 120V thermostat) in a dwelling unit?

NEED ALL REQUIREMENTS

What are: Calculated service demand is greater than 250 KVA, and there is a qualified electrical maintenance worker available

Rule 2-110 (a) 

500

What is the current carrying capacity of a #4 R90 single copper conductor when the ambient temperature is 80° C, using free air rating?

What is 140 x .41 = 57.4 amps - Rule 4-004 (7)(b)(i) and Tables 1 and 5A

 

                                                     

500

Are #8 RW90 XLPE copper conductors allowed as service conductors when installed in an underground conduit?

What is Yes - Rule 6-300 (1) (a) and 12-102 (3) and Table 19    

500

An electric range in a residential occupancy has a rating of 11 kW at 120/240 Volts. What is the minimum copper wire size required by the code if N.M.S.C. (Lumex) type NMD90 is to be used. What is the largest size two-pole breaker that is permitted by the code for this installation? 75 degree Equipment Termination Temperature Ratings 

What is #8 AWG and 40A 2-pole breaker 

Rule 8-300 (1)(a) and Table 2 

500

You are using Teck Cable as a service cable.  Is a bonding bushing required at the point of entry into the panel?

What is Yes (bond conductor is NOT in continuous contact with the armour in Teck cable)

Rule 10-604 (2)

500

What is the maximum number of #12 T-90 nylon conductors according to the code, which may be pulled into a #27 (1”) trade size PVC conduit?

What is 23

Rule 12-910-5  and Tables 8, 6K, 9G

500

Generally, 3 #2 XLPE RW75 conductors are considered protected by a 125 amp circuit breaker.

What is True (Yes)

14-104-1-a and Table 13