The minimum circuit size for the required laundry room circuit
20 Amps
210.11(C)(2)
Distance from the sink that would require a receptacle to be GFCI protected
Within 6ft
210.8(A)(7)
An area including a sink (basin) with one or more of the following: a toilet, a urinal, a tub, a shower, a bidet, or similar plumbing fixtures.
Bathroom
Article 100 - Definitions
Minimum distance multiple Grounding Electrodes can be installed apart from each other.
6ft
250.53(B)
Ungrounded Conductor
Hot Wire
The copper wire size and breaker size for this AC

8AWG and 50 Amp
440.6(A)
Distance of depth required in front of the panel
3Ft
110.26(A)(1)
An enclosure that is designed for either surface mounting or flush mounting and is provided with a frame, mat, or trim in which a swinging door or doors are or can be hung
Cabinet
Article 100 - Definitons
Minimum size ground wire that can be re-identified with green tape
4AWG
250.119 + (A)
NM Cable
Romex
The Minimum size service conductor for a dwelling unit 150 Amp service
1 AWG
310.12(A) + Table 310.12
Distance required between receptacles in general wall space
12ft
210.52(A)(1)
Locations protected from weather and not subject to saturation with water or other liquids but subject to moderate degrees of moisture
Location, Damp
Article 100 - Definitions
A building or structure supplied by a feeder shall have _____ installed
a grounding electrode system
250.32(A)
Overcurrent Protective Device (OCPD)
Breaker
The minimum size copper ground for a 100 Amp circuit
8AWG
Table 250.122
The smallest size kitchen counter top that requires a receptacle
12in
210.52(C)
All circuit conductors between the service equipment, the source of a separately derived system, or other power supply source and the final branch-circuit overcurrent device
Feeder
Article 100 - Definitions
The condition when an intersystem bonding termination device is NOT required
Where no communications systems are likely to be used
250.94 Exception to (A) and (B)
Grounding Electrode
Ground Rod
The minimum size THWN-2 wire for a 30 amp circuit with 14 conductors in a raceway
6 AWG
Table 310.15(C)(1)
Table 310.16
The max distance that equipment can be considered "within sight of" other equipment
50ft
Article 100, Definition - In Sight From (Within Sight From, Within Sight)
An electrical source, other than a service, having no direct connection(s) to circuit conductors of any other electrical source other than those established by grounding and bonding connections
Separately Derived System
Article 100 - Definitions
A grounded circuit conductor shall be permitted to be connected to non-current-carrying metal parts of equipment, raceways, and other enclosures at what location?
On the supply side or within the enclosure of the service disconnecting means
250.142(A)
Equipment Grounding Concuctor
Ground wire (for Branch circuits and feeders)