Loop the loop
It's getting hot in here
Bugging out
Tower of power
We have chemistry
100

A pressurized vessel used to dose chemistry to a chilled water loop

What is a bypass feeder

100

The process of opening a valve to release water from a boiler

What is blowdown 

100

A type of bacteria that survives in the absence of oxygen

What is anaerobic 

100

Also the last name of the ghost in 'A Christmas Carol', this cooling tower manufacturer is known for their open ended induced draft design

What is Marley

100

This biocide is just water with an extra oxygen atom

What is hydrogen peroxide

200

This metal is a component of many closed loop treatments and is common in loops containing aluminum

What is molybdenum 

200

This oxygen scavenger is usually catalyzed with cobalt for a quicker reaction time in steam boiler systems

What is sulfite

200

A common bacteria in laboratory studies, this bug is often indicative of fecal contamination and can cause gastrointestinal distress

What is e.coli

200

Measured in microsiemens typically, this reading is used to control bleed in a cooling tower

What is conductivity

200

This component, commonly found in antifreeze, is also an excellent food source for bacteria in a system

What is glycol

300

This inhibitor component is specifically designed and added to our treatment products to prevent corrosion of yellow metal components such as copper

What are azoles

300

This boiler system component can be tray or spray type and when used properly is effective at mechanically removing oxygen from boiler feed water.

What is a deaerator (DA) tank

300

Abbreviated to cfu, this is the measure per milliletre of bacterial activity in a water sample

What are colony forming units

300

This type of cooling that allows cooling towers to reject heat so effectively

What is evaporative cooling

300

This soft metal is alloyed with iron to create galvanized coatings

What is Zinc

400

When a chilled water loop is losing nitrite but there are no water losses and the conductivity does not drop we suspect this is happening

What is nitrite reducing bacteria 

400

This type of steam boiler typically has components called a mud drum, steam drum and risers 

What is a water tube boiler

400

Smaller than bacteria, these species are removed by sub nano filtration and are a major cause of illness worldwide

What are viruses

400

These plastic components help stop water droplets from leaving a cooling tower with the air flow

What are drift eliminators

400

This metal, common in plastic injection molding tools, is also found in most antiperspirant deodorants

What is aluminum

500

Used in high pressure high temperature hot water loops, this chemical is also an excellent oxygen scavenger and system passivator

What is DEHA

500

Named for two people, this valve is common to control water levels in a fire tube boiler

What is a McDonnell Miller valve

500

This type of corrosion is very damaging and is often found underneath biofilms in hydronic systems 

What is microbiological induced corrosion 

500

This type of evaporative cooling system does not have a tower fill but instead has a tube bundle inside the tower where heat exchange occurs

What is an evaporative condenser (fluid cooler)

500

These compounds with an -NH2 group in an organic molecule are common condensate treatment program components

What are amines