Core
Type 1
Type 2
Type 3
Radom
100

Which exams does a technician need to pass in order to obtain a universal certification?

Core + Type I + Type II +Type III

100

 Which are recommended safe work practices when recovering refrigerant

Wear safety eyewear and blue-lined gloves when connecting/disconnecting hoses

100

 When trying to figure out the leak rate calculations on a package unit. What information can you use?


Charge stated on name plate

100

Low pressure appliances operate...


In a vacuum or below atmospheric pressure.

100

What is the normal position of a service valve " king valve"?


Back seated

200

A technician with a Type III certification can repair what type of appliances?


Low pressure appliances such as chillers

200

When R-410A is recovered from an appliance, it

  1. Should be recovered into a recovery vessel that is clearly marked to ensure that mixing of refrigerants does not occur.

200

How long must an HVAC servicing company keep records for each disposed app charge between 5 and 50 pounds?




3 years



200

Where does the purge unit take its suction from?


The top of the condenser

200

When could a reciprocating compressor can be damaged if energized?


When the discharge service valve is closed

300

Can you work under someone else's certification?

No

300

What is the maximum allowable factory charge of refrigerant for type 1 appliances using CFC’s, HCFC’s, or HFC’s?


  1. 5 pounds

300

A company uses a chiller that diverts 55% of its cooling capacity to one of its manufacturing lines and 45% of its cooling capacity to air condition the office spaces. Which leak rate category would this chiller be in?


Industrial process refrigeration

300

What do CFC-11, HCFC-123, HFC-245fa, and HFO-1233zd have in common?

They are low pressure refrigerants that have high boiling points

300

How long does an owner have to repair a leaking low pressure appliance to below the leak rate threshold and get an initial verification test?


30 days

400

ODP stands for Ozone Depletion Potential which measures a substance's ability to:

Destroy ozone molecules in the stratosphere

400

For which refrigeration systems/appliances would it be permissible to use a passive recovery device for recovery of CFC’s, HCFC’s, and HFC’s?



A domestic refrigerator

400

When first inspecting a hermetic system known to be leaking, you should look for;


traces of oil.

400

What is the most effective way to leak test a charged low pressure chiller?


Use controlled hot water or electric heating blankets to increase system pressure

400

What can happen when a low pressure appliance has a leak at a fitting or gasket?

Air and moisture can enter the system

500

What do CFCs contain

Chlorine, fluorine, and carbon

500

When using a self-contained recovery device on a CFC, HCFC, or HFC system with an operating compressor, technicians must;


Either recover the refrigerant to 4 inches of mercury vacuum or 90% of the nameplate charge.

500

A cold storage warehouse chooses not to repair an appliance containing R-22 that is leaking above the threshold rate. How long can the facility continue to operate that appliance before it must be retrofitted or retired, assuming no extensions apply?


12 months

500

Why should a technician NEVER add nitrogen to a charged low pressure appliance for the purposes of leak detection?


It will cause the purge unit to operate resulting in refrigerant loss

500

 

When installing any type of access fitting onto a sealed system;



The fitting should be leak tested before proceeding with recovery.

M