100

Audible alarm notification devices shall provide a sound level of _____ dBa above the average ambient sound level or ___ dBa above the maximum sound level having a duration of at least 60 seconds, whichever is greater, in every occupied space

15/5 dBa

100

Spacing of detectors on a smooth ceiling shall be ___

30'

100

A device which detects the visible particles of combustion is a ____ detector

Smoke

100

Detectors shall not be installed until after

Final clean up of all trades

100

Smoke detector sensitivity shall be tested 

within one year of installation and every other year after

200

A _____ is an unwanted activation of signaling or an alarm initiating device in response to a stimulus or condition that is not the result of potentially hazardous condition

Nuisance Alarm

200

The most commonly used scale in drawings is

1/8" = 1 inch

200

what type of fire alarm system transmits alarm to a public emergency fire service communications center

Municipal fire alarm system

200

smoke detectors shall not be located near

Air supply diffusers

200

Secondary power supplies for fire alarm systems must operate that system in standby for a period of at least

24 Hours

300

The minimum decibel level for a fire alarm signal for a sleeping area is

75 dba

300

Ionization smoke alarms with an alarm silencing switch are not to be installed less than ____ horizontally from a permanently installed cooking appliance

10 feet

300

Horns, bells, and chimes are ___ appliances

Notification

300

smoke detectors shall not be located directly in the air stream of

supply registers

300

All household fire alarm equipment should have enough back up power to sound an alarm for _____ minutes

400

a signaling method characterized by simultaneous or sequential transmission on both, and reception of multiple signals on a signaling line circuit, a transmission channel, or a communications channel, including means for positively identifying each signal.

Multiplexing

400

smoke detectors must be installed within ______ feet of a door to a sleeping room

21 feet

400

The name of photoelectric light obscuration where the beam spans the protected area is ___

Projected beam smoke detector

400

smoke detectors installed within _______ feet of cooktop or range must be of the _____ type

20 feet/photo

400

single and multiple stations smoke alarms shall be tested after the initial installation test every ____

1 year

500

Where audible appliances are installed in mechanical equipment rooms, the average ambient sound level is

85dba

500

Wall mounted audio-visual notification appliances must be at least 6 feet 8 inches above the floor, but no more than ____ above the floor

8 feet

500

Fire alarm specifications are usually developed by this person who is also responsible for designing the system

Engineer

500

you must be certified by the of Ohio if you are ___

installing fire pumps, fire alarm systems, testing and inspecting fire alarm systems

500

A water flow device should be field adjusted so that an alarm is initiated in no more than _____ seconds

90

M