100

(BLANK) IS USED AS THE BASELINE MEASUREMENT FOR GWP.

carbon dioxide

100

WITH A INOPERATIVE COMPRESSOR, THE EQUIPMENT USED TO RECOVER MUST BE ABLE TO RECOVER (BLANK) OR THE REFRIGERANT OR ACHIEVE (BLANK) INCHES OF VACUUM.

80% or 4 hg

100

 A VACUUM LEVEL OF (BLANK) SHOULD BE ACHIEVED TO ENSURE ALL MOISTURE AND NON-CONDENSABLES ARE REMOVED

500 microns

100

A (BLANK) KIT IS USED TO DETERMINE IF A TUBE IS LEAKING

 hydrostatic tube test

100

A SINGLE CHLORINE ATOM CAN DESTROY UP TO (BLANK) OZONE MOLECULES.

100,000

200

 A RECOVERY TANK HAS A (BLANK) TOP AND (BLANK) BODY.

Yellow top and Grey body

200

WHEN FILLING A CHARGING CYLINDER, THE REFRIGERANT THAT IS VENTED OFF THE TOP MUST BE (BLANK)

recovered

200

IN THE SUCTION LINE, AT THE OUTLET OF THE EVAPORATOR, (BLANK) CAN BE FOUND

suction line accumulator

200

THE PRIMARY PURPOSE OF A (BLANK) IS TO REMOVE NON-CONDENSABLES THAT LEAK INTO A LOW-PRESSURE CHILLER SYSTEM.

purge unit

200

(BLANK) WAS ESTABLISHED TO PROVIDE COMPARISONS OF THR GLOBAL WARMING IMPACTS OF DIFFERENT GASES OVER A SPAN OF TIME.

global warming potential (GWP)

300

 A (BLANK) REFRIGERANT CYLINDER MAY NEVER BE USE TO RECOVER REFRIGERANTS.

disposable

300

BOTH (Blank) SHOULD BE INSTALLED WHEN RECOVERING REFRIGERANT FROM A HOUSEHOLD REFRIGERATOR OR ANY OTHER APPLIANCE TO IMPROVE THE SPEED OF RECOVERY.

high and low side

300

(BLANK) IS USED FOR CHECKING REFRIGERANT FOR MOISTURE AND (BLANK) SHOULD BE USED TO REMOVE ICE THAT HAS FORMED ON IT.

 sight glass, alcohol

300

WHEN MAKING A NON-MAJOR REPAIR, YOU SHOULD WARM THE LIQUID REFRIGERANT WITH (BLANK).

hot water or heating blankets

300

 (BLANK) TYPES OF REFRIGERANTS ARE SLIGHTLY FLAMMABLE.

A2L

400

A REFRIGERANT RECOVERY CYLINDER SHOULD NEVER BE FILLED MORE THAN (BLANK) OF ITS CAPACITY BY WEIGHT.

80%

400

 IF THE PRESSURE IS (BLANK) AFTER OPENING A PIERCING ACCESS VALVE, THE RECOVERY CANNOT BE BEGIN.

 0 pisg

400

ON THE HIGH SIDE OF THE COMPRESSOR, THE (BLANK) CAN BE FOUND.

discharge valve/line

400

 BE CAREFUL WHEN HEATING THE SYSTEM, SINCE THE (BLANK) ON A RECOVERY VESSEL, FOR LOW PRESSURE REFRIERANTS, RELIEVES A 15 PSIG.

rupture disc

400

 A (BLANK) SAMPLE SHOULD BE TAKEN THE UNIT HAS HAD A LEAK OR MAJOR COMPONENT FAILURE.

Oil

500

A REUSABLE CONTAINER FOR REFRIERANTS UNDER HIGH PRESSURE MUST BE (BLANK) TESTED EVERY 5 YEARS.

hydrostatically

500

A VACUUM PUMP MADE FOR SYSTEM DEHYDRATION MAY BE USED TO EVACUATE A RECOVERY CYLINDER TO BE USED AS A (BLANK)

 recovery device

500

IF (BLANK) REMAIN IN THE REFRIGERATION SYSTEM, THE DISCHARGE PRESSURE WILL BE HIGH.

non-condensables

500

THE HIGH PRESSURE CUT OUT CONTROL ON A RECOVERY UNIT USED FOR EVACUATING/RECOVERING THE REFRIGERANT FROM A LOW PRESSURE CHILLER IS TYPICALLY SET AT (BLANK).

10 psig

500

MVAC-LIKE SYSTEMS DO NOT MEET THE CRITERIA FOR (BLANK) APPLIANCE CERTIFICATION NO MATTER THE TYPE OF REFRIGERANT.

type 1