Cable Pulling Basics
Tools & Equipment
Safety First
Calculations
Miscellaneous
100

What should be used on all long vertical cable pulls?

Braking systems 

100

Name one of the 3 most commonly used fish tape materials 

Fiberglass, Steel, Nylon 

100

Before starting a cable pull, make sure what is in working order 

All communications equipment 

100

Five wraps on the capstan will provide how many lbs of pulling force 

512

100

One of the most common type of wire-pulling rope on the market?

Nylon

200

Mandrels should be approximately what percentage of the conduit size?  

80% 

200

The ideal device for lifting and transporting large cable reels 

Forklift 

200

Who is allowed to stop the pull at the first sign of danger to the cable, raceway system, or personnel? 

Anyone involved with the pull

200

In general, the pull exerted on cables pulled through trays using basket grip should not exceed 

1,000 lb

200

An important first step when planning and preparing for a cable pull

Measure the length of the run

300
Straight and swivel are the two types of what? 

Cable grips 

300

The ends of 1,000 kcmil conductors can be trimmed using 

Cable cutters 

300

Never pull a ____ fish tape through or into enclosures or raceways containing an energized conductor 

Conductive 

300

In general, the sidewall load on any raceway run should not exceed 

500 lb

300

Which factor determines the amount of force applied to a pull when using a power-operated cable puller (Greenlee G3) 

The number of wraps on the puller capstan 

400

The feed-in setup should unreel the cable how? 

along its natural curvature 

400

When one end of the pulling rope is attached to a cable grip; the other end is wrapped around the ____ at the cable puller 

Capstan 

400

When pulling cable with a capstan, what is the maximum pulling speed

40ft/min 

400

What is the total pulling tension for a cable weighing 3lbs/ft through 200' of conduit with a coefficient of friction of .35

210

400

To ensure a raceway is not damaged, this if often done prior to pulling conductors  

Test pull 

500

What precaution should be taken with conductors when making a cable pull in extremely cold weather 

Cable should be stored in a warm area overnight 

500

This meter measures pulling force during a cable pull 

Dynamometer 

500

Where is the safest place to stand while operating a power-operated cable puller  

Side of the machine 

500

What is the maximum length of cable weighing 6 lbs/ft that can be pulled through a
degree bend with a coefficient of friction of 1.48 using equipment with a maximum pulling
force of 5,000 pounds?

563'   (5,000=L x 6 x 1.48) 

500

To prevent pulling rope from burning through, these are typically installed for underground conduit runs 

Rigid 90's 