Plant 1
Plant 2
Mix
Lab 1
Lab 2
100

What is the Equalization basin volume?

240,000 gallons

100

What is the pumping capacity of one of the EQ pumps?

250 gpm

100

What is the maximum flow control set point as per the O&M?

3.0 mgd

100

What is the hold time for pH?

analyze within 15 min of collection

100

The BOD:COD for your facility's influent is 0.6.  If the COD of your influent is 360 mg/L, what is the approximate BOD of your influent?

200 mg/L

200

What is the Wet Weather basin volume?

100,000 gallons

200

What is the pumping capacity of one of the wet weather pumps?

400 gpm

200

What is our in house maximum flow control set point?

2.2 mgd

200

Cadmium-reduction technique is used when analyzing

Nitrate Nitrogen

200

Where would you find TC and what does it mean?

on pipettes/ graduated cylinders

To Contain

300

What is the Wet Weather Pond volume?

600,000 gallons

300

What is the pump start set point for the EQ pumps?

26”

300

What is the hold time for Total Phosphorus 

28 days

300

For the phenate method of ammonia analysis, at what wavelength should the spectophotometer be set?

515   -   530   -   615   -   630   

630

300

which test in the permit lab can also be referred to as the Diazotization Method?

Nitrite

400

The flow through channel is 10’x12’x29’. How many gallons of FSE will it hold without over flowing?

26,030 gallons

400

What is the pump stop set point for the EQ pumps?

20”

400

What is the hold time for Ortho Phosphate

48 hours

400

What is the proper temperature of a drying oven used in the determination of Suspended Solids

104 C +/- 1

400

What acid is used for NH3, TP, TKN preservation in our lab

H2SO4

500

What are the dimensions of the flow through channel?

29’x12’

500

What 4 conditions will close the primary effluent valve?

Anoxic Basins Lift Pump No Permissive to Run form Membranes

Anoxic Basin Lift Pumps All Off

Anoxic Basins 1 or 2 Level High-High

Control Building PLC-1 to PLC-2 Loss of Communication

500

What is the purpose of Na2S2O3 in a coliform bottle?

To remove any residual chlorine

500

What is TSS?

Material retained after passing the sample through a standard glass fiber filter

500

The oxygen depleted during the 5-day BOD test is used by which of the following?

Microorganisms

M