Articles 330
MC Cable
Article 340
UF Cable
Article 342
IMC
Article 344
RMC
Article 358
EMT
100

Type MC cable installed through, or parallel to, framing members shall be protected against physical damage from penetration by screws or nails by 1 1/4 in. separation or protected by a suitable metal plate. 

True or false?

True 

330.17

100

Type _____ cable is a factory assembly of conductors with an overall covering of nonmetallic material suitable for direct burial in the earth.

UF

340.2 Underground Feeder and Branch-Circuit Cable, Type UF

100

When IMC is cut in the field, reaming is required to remove the burrs and rough edges. True or false?

True

342.28  

100

Type RMC conduit shall be permitted to be installed where subject to severe physical damage. True or false?

True

344.10(E)

100

EMT run between termination points shall be securely fastened within _____ of each outlet box, junction box, device box, cabinet, conduit body, or other tubing termination.

3 ft

358.30(A)

200

Type _____ cable is a factory assembly of insulated circuit conductors within an armor of interlocking metal tape, or a smooth or corrugated metallic sheath.

MC

330.2 Metal Clad Cable, Type MC

200

Type UF cable is permitted to be used for inside wiring. True or false?

True

340.10(4)

200

Trade size 1 IMC run straight with threaded couplings shall be supported at intervals not exceeding 12 ft. True or false?

True

342.30(B)(2) and Table 344.30(B)(2) 

200

Horizontal runs of RMC supported by openings through _____ at intervals not exceeding 10 ft and securely fastened within 3 ft of termination points shall be permitted.

5

344.30(A)(2)

200

When EMT is installed in wet locations, all supports, bolts, straps, and screws shall be _____.

protected against corrosion 

358.10(D)

300

Type MC cable shall be supported and secured by staples; cable ties _____ for securement and support; straps, hangers, or similar fittings; or other approved means designed and installed so as not to damage the cable.

listed and identified 

330.30(A)

300

Type UF cable can be used for service conductors. True or false?

False

340.12(1)

300

A run of IMC shall not contain more than the equivalent of _____ quarter bend(s) between pull points such as conduit bodies and boxes.

four 

342.26

300

Stainless steel and aluminum fittings and enclosures shall be permitted to be used with galvanized steel RMC, and galvanized steel fittings and enclosures shall be permitted to be used with aluminum RMC where not subject to _____.

severe corrosive influences 

344.14

300

EMT shall be securely fastened in place at intervals not to exceed _____ ft.

10

358.30(A)

400

Smooth-sheath Type MC cable with an external diameter not greater than 3/4 in. shall have a bending radius not less than _____ times the external diameter of the cable.

Ten

330.24(A)(1)

400

The ampacity of Type UF cable shall be that of _____ conductors in accordance with 310.14.

60°C 

340.80

400

IMC, elbows, couplings, and fittings shall be permitted to be installed in concrete, in direct contact with the earth, or in areas subject to severe corrosive influences where protected by corrosion protection _____ for the condition.

approved 

342.10(B)

400

A run of RMC shall not contain more than the equivalent of _____ quarter bend(s) between pull points such as conduit bodies and boxes.

four

344.26

400

EMT shall not be used where _____.

subject to severe physical damage or used for the support of luminaires or other equipment except conduit bodies no larger than the largest trade size of the tubing 

358.12(1) and (2)

500

Type MC cable shall not be used under which of the following conditions?

Where subject to physical damage, Direct buried in the earth or embedded in concrete unless identified for direct burial, Exposed to cinder fills, strong chlorides, caustic alkalis, or vapors of chlorine or of hydrochloric acids 

330.12

500

Type UF cable shall not be used in _____.

motion picture studios, storage battery rooms, and hoist ways 

340.12(4), (5), and (6)

500

Where IMC enters a box, fitting, or other enclosure, _____ shall be provided to protect the wire from abrasion unless the design of the box, fitting, or enclosure affords equivalent protection.

a bushing 

342.46

500

Rigid metal conduit (RMC) shall be securely fastened within _____ ft of each outlet box, junction box, device box, cabinet, conduit body, or other conduit termination.

3

344.30(A)(1)

500

The use of EMT shall be permitted for both exposed and concealed work in _____.

concrete, in direct contact with the earth, or in areas subject to severe corrosive influences where installed in accordance with 358.10(B), dry, damp, and wet locations, any hazardous (classified) location as permitted by other articles in this Code 

358.10(A)(1), (2), and (3)