Airflow Control Valves
Room Pressure Controls
Healthcare Design
Pharmacy Design
Laboratory Design
100

Another name to describe what the VFX is

What is a high accuracy terminal unit?

100

Type of room pressure control that will maintain CFM difference between the supply and exhaust, even when the door opens/closes

What is Volumetric Offset Control?

100

Permanently installed device to constantly monitor the room differential pressure as per ASHRAE 170

What is a pressure monitor?

100

Pharmacy standard that covers non-sterile compounding

What is USP 795?

100

Primary goal is to protect the user by maintaining face velocity through the opening of the hood

What is a fume hood?

200

This allows airflow control devices to maintain constant airflow when there are changes in duct static pressure

What is pressure independence?

200

Reheat or cooling coil will operate from 0-100% at the same time airflow is added to the room

What is synchronous temperature control?

200

Design criteria that can be reduced when an isolation or operating room is not in use

What is ACH?

200

Type of primary engineering control (PEC) that is divided into 3 classes and often used for preparations of hazardous drugs

What is a biosafety cabinet (BSC)?

200

Device that maintains constant airflow regardless of sash height

What is a constant volume fume hood?

300

Most common type of coating used on VV/VFX in corrosive fume hood applications

What is Phenolic Class 1 coating?

300

Most important design consideration when designing pressurized spaces for critical applications

What is a properly sealed room?

300

Type of isolation room that requires an ante room

What is an Airborne Infectious Isolation with Protective Environment (AII-PE) room?


300

Involves creating medication in a clean environment, but does not require the environment to be completely free from all microorganisms

What is non-sterile compounding?

300

Airflow = _____ x Face Velocity

What is the open fume hood area?

400

Turndown of a Medium Pressure size 108 Venturi Valve (VV)

What is 20:1?

400

Requires room pressure sensor and some sort of display (i.e. local monitor, front end system, etc)

What is room pressure monitoring?

400

Minimum number of outdoor ACH for an isolation room

What is 2 ACH?

400

Minimum pressure relationship for sterile ante rooms

What is +0.02 in.w.c.?

400

Type of fume hood control that utilizes a sash position sensor and sidewall velocity sensor

What is hybrid control?

500

Name of the third party accreditation for the Antec Controls valve airflow testing rigs

What is NVLAP?

500

Accessory that is highly recommended to include when performing direct pressure control, in addition to the room pressure sensor

What is the door contact switch (DCS)?

500

Short-term excursions from required pressure relationships shall be allowed during this scenario

What are doors moving or temporarily open?

500

Minimum ACH requirement for non-sterile and non-hazardous compounding

What is 4 ACH?

500
Approximate cost of ventilation as per ANSI Z9.5, including energy required to move and condition supply and exhaust air

What is $3-$9 per CFM per year?