Ohm's Law
Definitions
Article 210
Article 250
Article 300
100

EMF stands for 

Electromotive Force 

100

Capable of being reached for operation, renewal, and inspection 

Accessible (as applied to equipment)

100

According to article 210, the following equipment can not be reconditioned 

1. GFCI Equipment for personal 

2. AFCI Equipment 

210.2

100

A conductive path(s) that is part of an effective ground-fault current path and connects normally non-current carrying metal parts of equipment together and to the system grounded conductor or to the grounding electrode conductor or both.

EGC

Equipment Grounding Conductor

100

________ in raceways shall be continuous between outlets, boxes, devices, and so forth. There shall be no splice or tap within a raceway unless permitted elsewhere in the code. 

Conductors

300.11(A)

200

The intensity of current flow is measured in

Amperes 

200

The maximum current, in amperes, that a conductor can carry continuously under the conditions of use without exceeding its temperature rating

Ampacity

200

The Grounded conductor of a branch circuit shall be identified in accordance with article 

200.6

200

What size Grounding Electrode Conductor do you need if the largest ungrounded conductor is a #1 copper

#6AWG

Table 250.66

200

According to the Conductor Applications and insulations rated 600Volts what two types of locations can you install RHH

Dry and Damp

Table 310.4(1)

300

Voltage is the same across all resistors in what type of circuit

Parallel 
300

A unit of an electrical system, other than a conductor, that carries or controls electric energy as its principal function

Device

300

What article covers GFCIs for personnel 

210.8

300

What size main bonding jumper is required if the largest ungrounded conductor is 4/0 copper

#2 AWG

Table 250.102(C)(1)

300

 What size Single-phase dwelling service conductors would you need for a 125amp service. 

#2 Copper

Table 310.12(A) 

400

The total current of a parallel circuit with three resistors each having 20 amps of current. 

20/3 = 6.7 amps

 

400

All circuit conductors between the service equipment, the source of a separately derived system, or other power supply source and the final branch-circuit overcurrent device

Feeder
400

Receptacle outlets in or on floors shall not be counted as part of the required number of receptacle outlets unless located within ____ of the wall

18 Inches 

210.52(A)(3)

400

What is the minimum size Equipment Grounding Conductor needed for a 800 amp OCPD

1/0 copper

Table 250.122

400

What is the ambient temperature correction factor based on 127 degrees Fahrenheit with a conductor temperature rating of 75 degrees Celsius 

.67

Table 310.15(B)(1)(1)

500

Total resistance in a parallel circuit with two resistors. One resistor has 16 ohms of resistance and the second resistor has 13 ohms of resistance

RT = (R1xR2)/(R1+R2)

RT = (16x13)/(16+13)R

RT = 208/29

RT = 7.20

500

The basic photovoltaic device that generates dc electricity when exposed to light

Photovoltaic Cell / Solar cell
500

At least one receptacle outlet shall be installed in bathrooms within ___ of the outside edge of each sink

3 feet

210.(D)

500

What article speaks to needing to separate the grounded conductor from the non-current carrying metal parts of the circuit after the main disconnect (load-side of equipment)

Article 250.142(B)

500

In cubic inches what is the minimum size junction box needed for five #6AWG conductors 

5 cubic inches x five #6 AWG conductors = 25 cubic inches

Table 314.(B)(1)