Wire Sizing
Grounding/Bonding
General Knowledge
Motor Circuits
Motor Knowledge
100

A single-pole breaker in a 120/240-V, 1-ph, 3-W panel supplies power to a motor circuit consisting of the smallest permitted conductors. The largest permitted DETD fuses are installed in a safety switch for the 115/230-V, 1Ø, 1 hp motor. The minimum size EGC permitted for this installation is ___ AWG. *

14 AWG

Table FLC = 16 amps   ->  1.75 X 16 = 28  30 A fuse  10 AWG

versus 16 X 1.25 = 20 A  14 AWG   

EGC not req’d to be > 14 AWG

100

NEC® Table ___ is used to size the conductor installed between the ground bar and the neutral bar in a service panel. *

NEC 250.102(C)(1)

100

An effective ground-fault current path has ___. *

Continuity, Sufficient Ampacity, Low Impedance

100

A motor has the following nameplate information:

208V  3ph      15 HP         42 Amps        1.15 Service Factor

The initial overloads were not sufficient to run the motor.  What is the new rating of the overloads? *

58.8 A

NEC 430.32

100

A 3-phase motor can be reversed by swapping any two circuit conductor connections at what location? *

Load side of starter, Terminal box at the motor, line side of starter, Load side of safety switch

200

The smallest THHN/THWN copper grounded conductor that can be installed for a service is ___ when the ungrounded conductors are 1/0 THWN/THHN copper and the load on the neutral is expected to be 120 amps.

1 AWG

T. 250.102(C)(1)_vs_T. 310.16


200

Rod and pipe electrodes are defined and described in ___. *

NEC:  250.52(A)(5)

200

How does grounding prevent an electrical fault? *

It Doesn't

200

The nameplate for a 15 HP, three-phase motor shows an FLA of 35 amps at 230 volts. What minimum size SOO cord is required to connect the motor to the branch circuit? *

4 AWG SOO Cord

Table FLC = 42 amps  ->  42 X 1.25 = 52.5 A  4 AWG

200

Circuit conductors (14 AWG) are installed between a 3-pole, 40-A circuit breaker in a panel and a motor. The circuit breaker protects the conductors against ___. *

Short circuit, Ground fault

300

Motor Nameplate Information:  208-230/460-V     3Ø     100 hp    

Supply:  3-pole breaker in a 120/240-V, 3-ph, 4-W panel

Minimum size circuit conductors are ___ AWG/kcmil. *

Table FLC = 248 amps   -> 248 X 1.25 = 310 A -> 350 kcmil

300

The minimum size of an equipment grounding conductor for a circuit protected by an automatic overcurrent device rated at 100 amperes is a ___ AWG wire. *

8 AWG

NEC:  250.122 (Table

300

If a GEC were to be installed inside a “conduit” to protect it from physical damage, which "conduits" may be used? *

EMT, IMC, Sch. 80 PVC, RMC

300

The smallest permitted circuit conductors are to be installed to feed a 2 hp, 115/230-V, single-phase motor. The circuit is supplied from a 1-pole breaker in a 120/208-V, 3-ph, 4-W panel. The maximum permitted size ITCB was installed for the motor circuit. Under these conditions, the minimum size EGC permitted is ___ AWG. *

10 AWG EGC

Table FLC = 24 amps -> 2.5 X 24 = 60 A breaker  10 AWG

 24 x 1.25 = 30 A -> 10 AWG at 75º terminations  EGC not req’d to be > 10 AWG

300

“Heaters” are installed in motor starters to protect ___. *

The motor against overload

The branch circuit conductors against overload

400

A grounded conductor is to be pulled in with 500 kcmil THHN/THWN aluminum conductors as part of a 277/480-volt, 3Ø, 4-W service to a 300-amp fused safety switch. The maximum unbalanced load on the neutral will be 140 amps. The minimum size of the neutral is ___ AWG aluminum. *

3/0 AWG

140 amps -3/0 AWG   vs    T.250.102(C)(1) - 1/0 AWG

400

The minimum size of a grounded conductor in a conduit is based on ___.    

The size of the largest ungrounded conductor

The load the neutral must carry

400

Electrical systems that are grounded shall be connected to earth in a manner that will limit the voltage imposed by what 3 things? *

Line surges, Lightning, Unintentional contact with higher-voltage lines

400

Motor: 7 1/2 HP  208V  3 Phase

The branch circuit for the motor is supplied from a 120/208-volt, 3Ø, 4-wire panelboard. The maximum size ITCB that can be used on the motor branch circuit is ___ A. *

70 A ITCB

T.FLC=24.2    24.2 X 2.5 = 60.5

400

Size the overloads for a motor with the following nameplate information:

480 Volt - 3-phase      5 HP       4 Amps      50°C temperature rise *

4.6 A

500

A 225 KVA, 480 delta to 208/120-volt, 3-ph, 4-w transformer is to be installed. One conduit will be installed between this 225-amp panel and the transformer. The conduit will contain 3 each 4/0 ungrounded conductors and the smallest permitted size grounded conductor. Almost all the connected load is 3-phase.  The smallest grounded conductor you can install in the conduit to the 225-A PB is ___ *

2 AWG

250.102(C)(1)

500

Determine the minimum standard size (AWG or kcmil) main bonding jumper required for a service with two sets of paralleled 750 kcmil conductors.

2 x 750 kcmil = 1500 kcmil x 121/2% = 187.5 kcmil

187.5 kcmil from Table 8, Chapter 9 (next larger size)  4/0 AWG

4/0 AWG is the minimum size main bonding jumper permitted for this service.



500

T/F

An overload occurs when an electrical conductor or equipment is operated in excess of its current rating. *

True

500

Motor Nameplate Information:  208-230/460-V     3Ø     200 hp    

Supply:  3-pole breaker in a 120/208-V, 3-ph, 4-W panel

Minimum size circuit conductors are ___ AWG or kcmil where 3 paralleled sets of conductors are used. *

Table FLC = 528 amps  -> (528 X 1.25) ÷ 3 = 220 A  4/0 AWG at 75º terminations

500

The ___ is the rotating part of a 3Ø motor. *

Rotor