Section 8
Tables
Section 12
Section 26
Section 30
Fun & Weird
100

What is the allowable percentage of voltage drop on the feeder or branch circuit?

What is 3%

100

What table do we use for ampacity ratings of not more than 3 copper conductors in a cable or raceway?

What is Table 2

100

How much conductor must be left at each outlet for making joints?

What is 150mm

100

All 5-15R and 5-20R receptacles located in child care facilities must be what type?

What is Tamper Resistant.

100

Branch circuit voltages for lighting in dwelling units shall not exceed _______ to ground

What is 150 Volts

100

What 2 primary colors can be mixed together to make purple?

What are Red & Blue

200

When interlocks are used to prevent AC and Heat from operating at the same time, what is the deciding factor when calculating the demand?

What is the greater load

200

What table gives us ampacity correction factors for more than 3 conductors when using Tables 2 and 4?

What is Table 5C

200

What is the maximum number of bends allowed in a run of raceway when conductors are intended to be drawn in?

What is 4 (90°) bends

200

Receptacles located in washrooms equipped with a sink, must be located within _____ of that sink.

What is 1m

200

When a light fixture exceeds ______kg, it must be supported independently of the outlet box.

What is 23kg

200

What year did we land on the moon?

When is 1969

300

How many additional spaces need to be left in a panelboard at time of installation in a single dwelling?

What is 4

300

What table gives us the size of rigid conduit when calculating fill and includes the 40% factor?

What is Table 9G

300

What is the maximum voltage allowed between any 2 conductors when using NMD90?

What is 300V

300

Panelboards installed in dwelling units must be installed so that no operating handle of an OC device is more than ______ above the floor. 

What is 1.7m

300

Light fixtures need to be connected to conductors of at least _______ AWG

What is # 18

300

What type of alcohol is traditionally used in a margarita?

What is Tequila

400

What is the basic load for the first 90m² of living area in a single dwelling?

What is 5,000 watts

400

What table gives us the conditions of use, voltage & temperature ratings of flexible cords, equipment wire, etc?

What is Table 11A

400

What is the minimum distance NMD90 cable must be from the edge of studs when it is run through studs before requiring protection?

What is 32mm

400

There must be at least one 5-15R Split or 5-20R on an island counter space with a continuous long dimension of _____ or greater.

What is 600mm

400

The temperature rating of conductors used for the wiring of closely spaced show window lighting fixtures must not be less than ________

What is 125°C

400

At what age was King Tut when he became ruler of Egypt?

What is 9 years old

500

Conductors supplying a range in a dwelling must have a demand of _____ when the range does not exceed _______

What is 8kW and 12kW

500

What table gives us the ampacity for aluminum conductor neutral support cables?

What is table 36A

500

When using ganged, sectional boxes, they must be secured to metal or wooden boards that are at least ______ thick.

What is 19mm

500

No point in a hallway of a single dwelling shall be more than ______ from a duplex receptacle

What is 4.5m

500

"Type Non-IC" recessed luminaires must be at least ______ from combustible material.

What is 13mm