Class 1 & Class 2 Circuits #1
Class 1 & Class 2 Circuits #2
Class 1 & Class 2 Circuits #3
ESH & Cooling #1
ESH & Cooling #2
100

Assuming a doorbell circuit is not subjected to mechanical damage, it could be wired with type ELC conductors in a house with metal studs for interior walls.  The house is made of wood and is considered to be of combustible construction. True or False?

True

Rule 16-210

100

What class circuit would a 16 V door chime circuit installed in a dwelling unit be considered if it is supplied by a current limiting transformer of 40 VA.

Class 2

Rule 16-200

100

True or False. The only difference between Class 1 and Class 2 circuits is the voltage rating.

False

Rule 16-100 and 16-200

100
If ESH of 5kW and AC of 6kW can be used at the same time, what demand value would be used in the service calculation?

11kW

100

What is the term for a permanently installed heating unit that can be removed or replaced without damaging the building structure?

Heating fixture

Rule 62-102
200

A Class 2 circuit can be fed from a 24 V, 150 VA transformer. True or False.

False

Rule 16-200

200

What is the maximum fuse rating allowed for the protection of a Class 1 circuit where No. 16 AWG conductors extend beyond the equipment enclosure.

10A

Rule 16-104

200

When can you use #18 AWG aluminum conductor for Class 1 circuits?

This is not permitted.

Rule 16-110.

200

What is the term for a permanently installed heating unit that can supply heat to rooms or areas, either through pipes or ducts?

Central Unit

Rule 62-102

200

What is the term for a rigid or non-rigid laminated plane section in which the heating element is embedded between or in sheets of electrical insulating material?

Heating panel

Rule 62-102

300

The overcurrent protection requirements of a Class 2 circuit can be met if the current in a 30V circuit is limited to 3.4A. True or false.

False. 30 x 3.4 = 102 which is > 100

Rule 16-212

300

The overcurrent protection requirements of a Class 2 circuit can be met if the current in a 30V circuit is limited to 3.3A. True or false.

True. 30 x 3.3 = 99 which is less than 100

Rule 16-212

300

Conductors of Class 1 and Class 2 circuits can be run in the same raceway if they are separated by a barrier. True or False.

True

Rule 16-212 3)

300

What type of heating generates heat within electrical insulating and semiconductor materials under the action of a high-frequency electric field?

Dielectric heating

Rule 62-102

300

What type of heating generates heat by means of the application of a low AC voltage across an electrically conductive object with the resulting current directly heating that object?

Impedance heating

Rule 62-102

400

What is the minimum size of individual copper conductors to be pulled into a raceway for use in a Class 2 circuit?

#16 AWG

Rule 16-210

400

You can run the circuit for a doorbell in the same conduit as the 120 V circuit for the light at the front door. True or False?

False

Rule 16-212

400

What VA and voltage ratings must a transformer have in order for the circuit it supplies to be classified as a Class 1 extra-low voltage power circuit?

1000VA, 30V

Rule 16-004

400

A heating panel set having an input more than _____A shall be supplied by a branch circuit that supplies no other equipment.

30A

Rule 62-114 1)

400

An ESH has a rated current of 25A. What is the maximum rating of OC device (rated for 100% continuous operation) you can use for the branch circuit conductors of this heater?

35A

Rule 62-114 7b) - 25/0.8 = 31.25

Rule 62-114 8) and Table 13 allows us to use a 35A device

500

What is the maximum overcurrent protection on the primary side of a 60 V, Class 2 circuit to limit the power to 100 VA?

20A

Rule 16-202 2)

500

What is the allowable ampacity of a No. 20 AWG, 4-conductor LVT cable?

2.8A

Rule 16-210. Table 57. 3.5 x 0.8 = 2.8

500

What are the 3 types of Class 1 circuits?

Remote control, extra-low-voltage power and signal

Rule 16-000

500

What is the demand towards the main service for the ESH in an apartment building that has 30 suites with 3500 W of heating in each suite?

30 x 3.5kW = 105kW

First 10kW @ 100% = 10kW

Remainder @ 75% = 0.75 * 95kW = 71.25kW

10kW + 71.25kW = 81.25kW

500

What is the demand towards the main service for the electric furnaces in an apartment building that has 30 suites with 3500 W of heating in each suite?

105kW

Rule 62-118 4). Electric furnace loads are taken at 100% demand.