Electric Vehicle Charging #1
Electric Vehicle Charging #2
Pools, Mobile Home and Temp Wiring #1
Pools, Mobile Home and Temp Wiring #2
Pools, Mobile Home and Temp Wiring #3
100

Which of the following are NOT considered to be electric vehicles according to the CEC? Cars, trucks, golf carts, vans, and motorcycles.

Golf carts

Section 86

100

Which of the following would NOT be considered part of the electric vehicle supply equipment? Cables, connectors, battery, and fittings.

Battery

100

What is the minimum distance required between a luminaire and the pool water if it is not protected by a Class A GFCI?

3m

Rule 68-068

100

What size AND material of conductor is required to bond a steel ladder for a permanently installed swimming pool?

#6 AWG copper

Rule 68-058 8)

100

What type of luminaire must be accessible through a hand hole in the pool deck?

Dry niche luminaires

68-066 4)

200

What is the term for a device that connects the electric vehicle to the charging equipment that allows for the charging of the vehicle as well as exchanging information between the branch circuit and the vehicle.

Electric vehicle connector

200

What 2 energy sources would a hybrid-electric vehicle operate on?

electricity and gasoline

200

What is the maximum distance from a commercial hot tub or spa that the emergency shutoff switch shall be permitted to be located?

15m

68-404 4) c)

200

What is the minimum vertical clearance above a permanently installed pool for a neutral-supported cable operating at 1000V?

5m

68-054

200

What is the minimum vertical clearance above a permanently installed pool for a neutral-supported cable operating at 49,000V?

7.5m

68-054

300

What type of receptacle is used in a Level 1 charging station?

5-20R

300

Level 2 chargers can operate at either _____V or _____V.

208V, 240V

300

Receptacles located between _____m and _____m of the inside walls of a pool shall be protected by a Class A GFCI.

1.5m, 3.0m

68-064

300

Where temporary service equipment is installed outdoors, what is the maximum equipment rating when mounted on a single pole?

200A

76-006

300

What is the minimum horizontal distance from the edge of a residential swimming pool that 120/240 V single phase underground power conductors run in a PVC conduit can be located?

1m

68-056, Table 61

These are insulated conductors running in non-conducting raceway

400

Name 2 of the 5 types of indoor locations where it is permissible to install electric vehicle supply equipment.

Residential garages - either detached or attached

Enclosed or underground parkades

Commercial garages

Agricultural buildings

Similar areas

Rule 86-400

400

Up to what voltage and current can a Level 3 charging station operate?

600V, 600A

400

What 2 configurations of receptacles require Class A GFCI protection when installed to provide power for buildings or projects under construction or demolition?

5-15R and 5-20R

76-016

400

What other loads may be connected to a temporary lighting branch circuit?

Nothing. Lighting must be separate from power branch circuits.

76-012

400

With which section of the CEC must luminaires installed in temporary wiring systems comply?

Section 30

76-012

500

What must be provided for any electric vehicle charging station rated above 60A or above 150V to ground?

A separate disconnecting means

Rule 86-304 1)

500

Where there is no EVEMS present, what other loads can be connected to the branch circuit supplying the electric vehicle supply equipment?

Ventilation equipment intended for use with the electric vehicle supply equipment

Rule 68-300

500

Name the 4 types of receptacles permitted to be installed on RV lots.

5-15R / 5-20R / TT-30R / 14-50R

72-108

500

A 6000 W, 240 V electric heater is used for temporary heating. What is the minimum rating of circuit breaker required to protect this circuit?

35A

6000/240 = 25

76-012 -> 25/0.8 = 31.25

Table 13 -> 35A

500

What is the minimum ampacity of the consumer's service conductors for an RV park with the following receptacles (120/240V supply):

- 8 receptacles rated at 50 A, 125/250 V each

- 14 receptacles rated at 30 A, 125 V each

- 14 receptacles rated at 15 A, 125 V each.

First 9: (8*12kW)+(1*3.6kW) = 99.6kW

Next 6: (6*3.6kW)*0.9 = 19.44kW

Next 20: (7*3.6kW*0.8)+(13*1.8kW*0.8) = 38.88kW

Remainder: 1*1.8kW *0.75 = 1.35kW

Total = 159.27kW --> 159.27kW/240V = 663.625A

72-102 and Table 71