Patient Care Areas #1
Patient Care Areas #2
Patient Care Areas #3
Capacitor Banks #1
Capacitor Banks #2
100

An essential electrical system in a health care facility must contain at least _____?

A vital branch

24-302

100

What type of branch of an essential electrical system within a health care facility must power be restored to within 1 minute of a power failure?

Delayed vital branch

24-002

100

What equipment shall the emergency supply system consist of?

Onsite generator(s)

24-306

100

Where a branch circuit supplies two or more capacitors, the overcurrent device protecting the conductors of the branch circuit shall be considered as protecting the taps made to supply single capacitors provided the taps are not more than ____m long.

7.5m

26-208

100

The maximum rating or setting of the overcurrent device for a capacitor branch circuit conductor shall not exceed _____% of the rated current of the capacitor.

250%

26-210

200

What is an isolated system?

One in which no circuit conductor is connected directly to ground 

24-002

200

What type of system shall branch circuits in basic care areas be supplied from?

Grounded distribution system

24-104

200

What insulation colors shall be used in isolated circuits?

Orange and brown

24-204 2)

200

What is the required conductor ampacity of a capacitor rated at 150 A?

202.5A

135% x 150A

26-208 1)

200

What is the minimum calculated ampacity for a capacitor tap conductor when the branch circuit conductor supplying it has a rated ampacity of 36A?

12A

36/3 = 12A

26-208 2) b)

300

How shall all receptacles supplied from circuits in an essential electrical system be colored?

Red

24-108

300

Receptacles located in basic care areas that are routinely cleaned using liquids that normally splash against walls shall be installed not less than _____mm above the floor.

300

24-108

300

To which screw of the receptacle shall the orange-insulated conductor be connected in an isolated circuit?

Nickel

24-204 2)

300

What is the maximum rated current of a capacitor that may be connected to a branch circuit that uses a No. 8 AWG copper RW90 conductor? All equipment and terminations are rated at 75 °C.

Table 2 -> 50A

50/1.35 = 37.037A

26-208

300

A 600 V capacitor uses a permanently connected resistor to drain the stored charge on the capacitor to 50 V when disconnected. What is the maximum time period in which this must be accomplished? And what rule states this?

1 minute

26-222

400

Who is responsible for designating patient care areas within a health care facility?

Health care facility administration

400

What is the designation of an area within a health care facility that is an anesthetizing location, or in which cardiac contact between a patient and medical equipment is normal and frequent?

Critical care area

24-002

400

At the time of installation the total impedance between ground and each energized conductor of a single-phase isolated system shall exceed _____ Ω without utilization equipment or the line isolation monitor connected.

200,000

24-204

400

An open contactor rated for 70 A is to be used as the disconnect for a capacitor bank. 

What is the maximum rated current the capacitor bank can have?

70/1.35 = 51.85A

26-216

400

What is the maximum rating of overcurrent device for a single-phase, 3 kVAR capacitor rated at 240 V?

3000VAR/240V = 12.5A

250% x 12.5A = 31.25A (26-210)

Table 13 -> Select 30A since we are asked for the MAXIMUM rating


500

The patient care environment includes the space within _____m beyond the perimeter of the bed, table or other supporting mechanism and the space within _____m of the floor.

1.5m, 2.3m

24-002

500

What visual marker indicates that a receptacle is hospital grade?

Green dot

500

What is the purpose of a line isolation monitor?

Monitors impedance-to-ground of the system and together with any loads connected to it.

24-204 5)

500

In what connection scenario does a capacitor NOT require a discharge circuit or a separate disconnect?

Between the motor starter and the motor

500

In what connection scenario does a capacitor require a discharge circuit but NOT a separate disconnect?

Between the motor disconnect and the motor starter

26-218, 26-222

M