What is NFPA 70.
Who is responsible for properly maintaining a water-based fire protection system?
What is the owner or designated representative.
An organization, office, or individual responsible for enforcing the requirements of a code or standard, or for approving equipment, materials, an installation, or a procedure.
What is the Authority having Jurisdiction (AHJ)
The owner or owner's representative shall retain all maintenance reports for a period of _____ after the next maintenance of that type required by this standard.
What is 1 year.
Acceptable to the Authority Having Jurisdiction
What is approved.
Indicates a mandatory requirement.
What is "Shall"
As-built system installation drawings, hydraulic calculations, original acceptance test records, and device manufacturer's data sheets shall be retained for _____?
What is the life of the system.
This class of fire are fires in ordinary combustible materials, such as wood, cloth, paper, rubber, and many plastics.
What is Class A fires.
At least ____ , the date the inspection is performed and the initials performing the inspection shall be recorded.
What is monthly.
Pipe Joints other than threaded, welded, brazed, flared, compression, or flanged type shall be _____ or approved.
What is listed.
All required annunciation means shall be readily_____ to responding personnel.
What is "Accessible"
What is Black?
When manual inspections are conducted the ____ and ___ the manual inspection was performed and the initials of the person performing the inspection shall be recorded.
What is the month and year.
Pre-engineered systems shall be installed to protect _____ within the limitations of the listing.
What is hazards.
Plans and calculations shall be approved prior to ____
What is installation
Prior to system maintenance or testing, the record of completion and any information....shall be provided by the _____
What is the "owner or a designated representative"
____Personel shall be in attendance whenever the pump is in operation...
What is qualified.
The frequency of hydrostatic testing for halogenated agents according to 8.3
What is 12 years.
What is close
The system shall be _____ in accordance with the requirements of this standard and the manufacturer's design, installation, and maintenance manual.
What is tested.
The method for measuring speech intelligibility is?
What is Speech Transmission Index (STI)
Internal inspection of valves that can be reset without the removal of a faceplate shall be permitted to be conducted every ____
What is 5 years.
The pressure in a hydrostatic test of a cylinder shall be maintained for a minimum of ____ seconds, but for a time not less than is required for complete expansion of the cylinder and to complete the visual examination of the cylinder.
What is 30 seconds.
Maximum temperature limitation for dry chemical extinguishing systems shall be at least ____f
What is 120 degrees F.
Personnel that inspect, service, test, and maintain clean agent fire extinguishing systems shall have knowledge and experience of the maintenance and servicing requirements contained in this standard, of the equipment being serviced or maintained, and of the servicing or maintenance methods and requirements contained in the manufacturer’s design, installation, and maintenance manual and any applicable bulletins.
What is Fire Protection Service Technician.