Cable Locating
Underground System
Safety Manual
Underground Cables
Misc. I
Misc. II
Final Jeopardy
100

What are the two main types of locates performed during cable locating operations?

WHAT IS 

Active and Passive

100

What should be done prior to pulling cables?

WHAT IS 

swab conduits

100

What shall all undergroud circuits and equipment be considered as until disconnected from the source, tested for voltage, effectively grounded,  and tagged?

WHAT IS 

Energized

100

Cables are generally identified according to what?

WHAT IS 

Insulation type

100

According to rule 360, the mechanical protection of supply conductors on a riser pole should extend how far below ground level at the pole?

WHAT IS 

12 inches

100

What are the two main types of underground feeds?


What is

Loop Feed and Radial Feed


100

What is the PBT shield transformer bushing color coding and their KV rating

WHAT IS 

Red 15kv, Blue 25kv, Black 35kv

200
Which method of active locating is the best and preferred?

WHAT IS 

Direct Connect

200
What is a common cause of underground system cable faults

WHAT IS 

improper handling and installation of cable

200
What is required to perform energized switching for paralleling operations or to make/break load?

WHAT IS 

Load break elbows

200
The layer next to the conductor is called the ____ while the layer next to the concentric neutral or shielding is called the _____?

WHAT IS 

Strand sheild and insulation shield(Semi con)

200

!!DAILY DOUBLE!!

Rule 314C explains what circuits must be grounded at padmount transfomers. according to this rule what is the one exception?

WHAT IS 

High voltage DC

200

The recommended minimum burial depth of underground cable operating at 7,200 volts is ____ feet?

What is 

2.5ft

300

How many inches of clearance do you have on locate on each side?

WHAT IS 

18"

300

Excessive pulling tension can result in what three things

WHAT IS 

exceeding elastic limit of the conductor, stressing the extruded portions of the cable, excessive sidewall pressure at conduit radius 

300

Access to padmounted enclosures operating at greater than ____ shall required ___ conscious acts to open.

WHAT IS 

600v and 2

300

Name this cable

WHAT IS 

XLPE

300

A conductive communication pedestal and a pad mount transformer must be bonded if they are within ___ of eachother?

WHAT IS 

6ft

300

Grounded supply systems should not be operated in excess of ______ volts to ground?

What is 

22,000 volts

400

On a short locate is it important to keep your temporary ground perpendicular to the locate?

WHAT IS 

No

400

Name four types of transformers which are used in underground systems

WHAT IS 

Padmount, Submersible, Direct-buried, Vaulted

400

When responding to an outage call, you find the bayonet fuse opened and are not sure of the cause, how should you proceed?

WHAT IS 

you should not re-install bayonet fuse until you have tested and verified the transformer is not bad otherwise you must take an outage to re-install the fuse then re-energize from a remote location

400

What are the shields main purpose in underground cables

WHAT IS  

To evenly distribute the electric field 

400

what is the purpose of annular stranded conductor?

WHAT IS 

to combat the "skin effect" because AC flows more concentrated near the outer surface of a conductor

400

Fellow workers and by standers should be kept ____ feet away from working equipment. This is also known as the danger zone.

What is

6ft

500

How could a fence or metal object distort a signal formed with transmitter?

WHAT IS 

metal mass will steal the signal and return it when done

500

Name all six main components that an underground system would contain

WHAT IS 

Conduits or Ducts, Manholes, Cables, Vaults, Risers,Transformers

500

What are the five steps for removing a bay-o-net fuse?

WHAT IS 

1)operate pressure relief valve

2)Stand to side of transformer place shotgun stick in eye

3)Break seal by unlocking fuse eye and rotating it back and forth 

4)Slowly pull out fuse avoiding dripping oil outside of drip pan

5)As the tube comes out of transformer rest it on the drip pan before pulling away from transformer

500

What does TR-XLPE and EPR stand for?

WHAT IS 

 Tree-retardant Cross-linked polyethylene and Ethylene Propylene Rubber

500

What are all four types of hazards lineworkers encounter when working on de-energized cables?

WHAT IS 

1)Accidental re-energization

2)Induced voltage

3)Transfer of potential

4)Capacitor effect

500

What three reasons is positioning of the cable reel important?


What is 

1)To minimize cable flexing during pulling

2)To avoid reverse bends in the cable

3)To permit payoff of cable at controlled rate