NEC
Conduit
90 Bends
Offset Bends
Saddle Bends
100

This is Chapter 1

What is General?

100

Of the three primary metal raceway types, this one does not require threading

What is Electrical Metallic Tubing (EMT)?

100

When bending a 90bend, this is the end bent up into the air. Usually the shorter end.

What is the stub/stub up?


100

This is the most commonly used angle for bending offsets due to its easy to remember multiplier of 2.

What is 30 degrees?

100

In a three-bend saddle, you must add this variable to the center mark to keep your bend centered over the obstruction.

What is shrink?

200

Wiring Methods and what other topic are in Chapter 3

What is Materials

200

This is the Largest size EMT you can bend with a hand bender

What is 1 1/4"?

200

To make a stub 90o that is 39 inches long with 1/2" EMT (using a standard hand bender), you would need to place your pencil mark at this distance from the end of the conduit.

What is 34"?

200

This angle's distance multiplier is 1.41

What is 45 degrees?

200

Mathematically, a three bend saddle can be viewed as two of this other kind of bend put together.

What is an offset?

300

This chapter gives values for wire sizes

What is Chapter 9

300

This is the Largest size RMC you can bend with a hand bender

What is 1"?

300

Stub 90s are always measured to this side of the bend.

What is the back(outside) of the 90?

300

To bend an offset with 30 degree bends to clear an obstruction 4 inches high, the bend marks must be this far apart.

What is 8 inches?

300

To find the total overall length of a conduit with a three bend saddle you must add the shrink value this many times.

What is two?

400

This is the topic for Chapter 5

What is Special Occupansies

400

This article in the NEC gives all the code requirements for EMT.

What is Article 358?

400

To cut a conduit to the correct length before bending a 90o, you must first adjust for this.

What is the gain?

400

The smallest offset is

Box offset

400

When making calculations for a three-bend saddle, all calculations are made off of this bend angle

(Larger or smaller angle)

What is the smaller angle?

500

Name all topics 1-9 in order

General, Wiring and Protection, Wiring Methods and Materials, Equipment for General Use, Special Occupancies, Special Equipment, Special Conditions, Communications Systems, Tables

500

This is the support distance for EMT

What is 10'

500

What is the take-up for 1 1/4" EMT

What is 11"

500

Shrink for a 60 degree bend is

1/2"

500

The distance modifier for a 45 degree center 3 point bend

What is 2.5"

M
e
n
u