Troubleshooting
Coils
Parts
Evacuation
Readings
200

target temperature difference between supply and return

16-20 degrees


200

Fins on a coil increase

Surface area and heat transfer


200

Primary purpose of a metering device

Creates pressure drop

200

Pressure that is less than the surrounding pressure

Vacuum

200

The air temperature readings you need to know before assessing refrigerant pressures

Ambient temperature and return air wet bulb

400

Whats the main cause of a system to freeze up

Low airflow

400

If air velocity is too high across an evaporator it can decrease

dehumidification

400

What increases the pressure in a system

Compressor

400

Target goal when evacuating a system

500 microns

400

Readings needed to measure Suciton line superheat

suction line pressure and temperature

600

The coldest the liquid line can get

Is the temperature of the air or water it is rejecting heat to

600

The bent pieces of copper at the end of a coil

u-bends

600

Stores Excess liquid refrigerant and helps ensure only liquid is leaving condenser

Liquid Reciever
600

How do you get all of the moisture out of poe oil

Desiccants in a filter drier

600

the three pressure of air in a duct

Static, Velocity, and total pressure

800

Moisture in a refrigeration system causes

Acidity and compressor failure

800

the two main types of air coils are

microchannel and tube and fin

800

Installed on discharge line and absorbs noise and vibration

muffler

800

Methods to get more moisure and refrigerant out of oil during evauation.

Heat oil up, shake it, blast nitrogen through it (triple evac).

800

The two readings you need to determine compression ratio

Discharge and suction pressure

1000

High superheat and low subcooling is a common sign of this

Undercharge

1000

The temperature at the midpoint of the coil should be

Saturation temperature of the refrigerant

1000

This can be installed in the suction after a burnout to absord acidity

Suction line drier

1000

What should you open when first starting your vacuum (especially if a lot of moisture is present) until about 1500-3000 microns.

Gas ballast

1000

Readings needed to determine unit airflow using fan performance chart

Return and supply static pressure (ESP)