Questions 1-5
Questions 6-10
Questions 11-15
Questions 16-20
Questions 20-25
100

. Equipment grounding refers to connecting the normally noncurrent-carrying metal parts of equipment to the system grounded conductor and/or _____.

the grounding electrode conductor

100

To be effective, a grounding system must limit the voltage on the electrical system and protect it from _____.

voltage surges

100

Which of the following is TRUE when two or more equipment grounding conductors enter an outlet box?

The grounding conductors are first connected using an approved method, then one wire is connected to the grounding terminal on the receptacle.

100

The bonding jumper for multiple disconnecting means is located _____.

on the supply side of the service disconnect

100

A ground tester can be used to measure the value of a grounding electrode's _____.

resistance

200

A ground fault is described as an unintentional _____.

electrically conducting connection between an ungrounded conductor in a circuit and the normally noncurrent-carrying conductors

200

Service conductors are sized using _____.

NEC Table 310.16

200

If single-gang, nail-on, nonmetallic boxes are used with NM cable, which of the following is TRUE regarding grounding conductor connections?

No grounding conductor connection to the box is required

200

A generator system that supplies power where the neutral is not connected to the utility system, such as for carnivals, is known as a(n) _____.

separately derived system

200

How many ungrounded conductors must be taken from the first structure to where the service is located in the second structure when running 120V between buildings?

1

300

 AC systems over 1kV that supply mobile or portable equipment

type of system is required to be grounded?

300

The minimum length allowed for driven ground rods under normal conditions is _____.

8'

300

The main bonding jumper is sized based on the size of the _____.

service conductors

300

Which of the following is TRUE of the neutral in a grounded system?

It provides a low-impedance return path for the flow of fault current to the source.

300

The fall-of-potential method is used to measure _____.

earth resistance

400

A transformer-supplied system operating at less than 50V must be grounded if the supply voltage to the transformer exceeds _____.

150V to ground

400

The metallic noncurrent-carrying parts of an electrical system are bonded together to ensure _____.

the proper operation of overcurrent devices in the event of a ground fault

400

The key to successfully clearing ground fault currents is _____.

electrical continuity

400

The grounded circuit conductor and the equipment grounding conductor must both be extended to the second building

when installing grounding at more than one building?

400

A ground test utilizing an auxiliary current electrode and an auxiliary potential electrode is known as the _____.

three-point test

500

A ground ring consisting of 20' of No. 2 bare copper must be buried no less than _____.

2.5' below grade

500

The size of the equipment grounding conductor is determined by the size of the _____.

system overcurrent device

500

According to the NEC®, the path to ground from circuits, equipment, and metal enclosures must _____.

provide a permanent and continuous path sized to safely conduct potential fault current

500

A transformer bonding jumper is routed with the feeder conductors from the transformer to the equipment grounding bar in the panel and is known as a(n) _____.

supply-side bonding jumper

500

When a new grounding system has been installed, it is advisable to conduct baseline three-point tests every _____.

season for the first year

M
e
n
u