Electrical
Electrical
V
V
V
100

Describe our electrical redundancy and what happens if we lose one line up.

DISTRIBUTIVE REDUNDANCY!

Another term used is “LOAD SHEDDING”

100

Define and describe a Circuit Breaker, to include:

A circuit breaker not only controls the flow of electricity in a circuit, but also provides overload protection by tripping

100

Define and describe the LSIG settings found on the Trip Unit of a circuit breaker.

LSIG signify the type of protection and available adjustments on certain trip units

L - Long time setting

Overload Protection

S - Short time setting

Low level fault short circuit protection

I – Instantaneous setting

High level fault short current protection

G - Ground fault setting

Equipment ground fault protection

100

a.  UPS: Primary and secondary function.

Primary – uninterruptible (U), continuous power to the load

Secondary - protected power (P), filters and conditions power, prevents damage to output

100

Explain the difference between Maintenance Bypass and Static Bypass. Describe in which situations Maintenance Bypass would be required.

Maintenance Bypass – used when performing maintenance on the internal components, diverts power away from the UPS altogether (externally)

Static Bypass – used when there is an internal fault or UPS failure, diverts power away from the rectifier-battery-inverter (internal)

200

Describe the type of batteries we use in our UPS systems, including:

Lithium-ion batteries

17 batteries in each of the 5 strings

b. How long we are able to keep load on battery (if loaded to design)

7 minutes

 Float voltage

Float voltage of 570v (the voltage at which a fully charged battery is maintained to prevent overcharging)

200

Define and describe a Circuit Breaker, to include:

b. Major external components and function of each

charging handle – when in open status, this charges the spring so the breaker may close

manual push buttons – used to manually close/open the circuit

Position – racked-in, test, disconnected, racked-out (withdrawn)

Status – open, closed, tripped, charged, not charged, OK

LOTO – safety measure to ensure equipment is safely shutdown and isolated

trip unit (not seen) – part that opens the contacts of a breaker in the event of a fault

200

Assuming proper permissions, are any of these trips safe to reset without a thorough breaker inspection?

For Long Term settings, only if engineering team understands what caused the trip

Any other trips requires a technician

200

 UPS: Model, Type, and Capacity

Schneider Galaxy VX

Double-Conversion

1MW

200

Describe a transformer, to include:

a. component function

b. types found on site

a.

to step-up or step-down voltages in circuits (AC)

note that DC cannot change voltages

b.

Delta – three loads connected in a triangle

Wye – three loads connected in a Y

*Wye transformers have a neutral wire which allow for single-phase (Delta does not)

300

Provide an in-depth explanation of the difference between Single-Phase AC power and Three- Phase AC power. Which one do we use for our critical loads and why.

Single-Phase AC power – one sine wave created by one hot wire and one neutral

Three-Phase AC power – three sine waves, 120˚ apart each with one hot wire and one neutral

Critical loads use 3-phase because it’s the most power efficient source

300

BREAKER STATUS

D.What does it mean when a breaker is tripped?

Open – no power thru circuit

Closed – power thru circuit

Tripped – fault in circuit

Charged – ready to close breaker

Not charged – not ready to close breaker

D.

300

Define the term Arc Flash. Why are they dangerous? In what maintenance scenario is an arc flash most likely to occur with the electrical system?

electrical explosion

Most likely occurs during EEM (Energized Electrical Maintenance), when closing a live circuit breaker

300

UPS: Major internal components and basic function of each

Rectifier – converts AC to DC power, then filters thru capacitors; trickle charges the batteries

Inverter – converts DC to AC power via Pulse Width Modulation (PWM), and again filters thru capacitors

Batteries – provides DC power to the inverter should the utility fail

Static Switch – internal to the UPS, diverts power from the rectifier-inverter-batteries to the load when there is a fault/failure within the UPS system

Back Feed Breaker – prevents the flow of electricity going backward

300

Difference between step up or step down transformer

Step-up transformers – voltage is higher on the secondary side, current lower

Step-down transformers – voltage is lower on the secondary side, current higher

400

Define AC and DC power and provide a brief description of each. Where are each utilized in the building?

DC power – direct current; used in batteries

AC power – alternating current; used everywhere else

400

Explain Open vs Closed Transition with respect to the electrical distribution system. Which do we use when going in and out of maintenance bypass? How about when load is transferred between Utility and generator?

Open transition – “break before you make” open contact with primary source, then closing the secondary (both contacts are open for a moment)

Closed transition – “make before your break” closed contact with primary source, then open the secondary (both contacts are closed for a moment)


During maintenance bypass, a closed transition is used

When load is transferred between utility and generator, an open transition is used



400

How are the Trip settings and the Arc Flash Labels related?

Arc flash ratings are determined by the trip settings

If the settings have changed, then the arc flash labels must be updated as it is inaccurate.

400

UPS: Modes of Operation

Normal

Static Bypass

Maintenance Bypass

On Battery

400

Effects of a transformer's turn ratio on output

Effects of a transformer’s Turn Ratio on output

turn ratio refers to the number of times a coil is wrapped (more turns, more voltage)

500

Define the following electrical parameters, to include their base measuring units and symbol.


Voltage, Current, Resistance, Power, Frequency, Phase

Voltage – pressure that pushes electrons thru circuit; Volts [V, KV]

Current – flow of electrons thru circuit; Amps [A]

Resistance – opposes current (flow); Ohms [Ω]

Power – work done in a circuit (P=IE), Watts [W, KW]

Frequency – the # of times AC completes full cycle in a second; Hertz [Hz]

Phase – distribution of AC power, a single-phase being one hot and one neutral wire

500

Explain the process of selective tripping. Why is it designed within the electrical system? How is it accomplished?

Selective Tripping means that when a fault occurs anywhere in the distribution system, one and only one breaker will trip

The tripped breaker will be upstream from the fault so a chain reaction would be prevented (cascading failure)

opening times are adjusted so the breakers closest to the faults open first

500

Define and describe UPS, to include:

UPS – Uninterruptible Power Supply

500
UPS: Sequence of Operation and Alarming Set Points

Sequence of Operation:

Under normal conditions, power goes thru rectifier, trickle charges the batteries, thru the inverter and to the load.


Alarming set points:

Over temperature

Inverter/Rectifier failure

Fan failure

Communication failure

Power Module failure

500

Define PDU and describe is function. Include in your description

PDU – Power Distribution Unit

Converts power (via transformer) and distributes to multiple devices

a. output power capacity

480v TO 415/240V and 208/120V

480V enters PDU and converts to dual tap 415/240V and 208/120V

Internal components:

Input breaker, voltage transformer, CT, sub-feed output breakers

Sequence of Operation: 

Distributed to output thru the sub-feed output breakers



M
e
n
u