Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA
What is the recommended quantity and size of the phase conductors?
#10AWG (NEC 430.22)
In a 208V, 3 phase circuit, what is the phase-to-phase voltage?
208V
What size breaker should the main of a 480V, 3ph, 1250kW, .8pf generator be?
2000A
Hoth
Star Wars The Empire Strikes Back
Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA
What table do I used to size the ground wire for the motor feeder?
Table 250.122 (NEC 250.122(D))
In a 3-phase, 4w system what should the ideal neutral-to-ground voltage be?
0V
What size breaker should supply a 480V, 3ph AHU/RTU with (6) 10HP motors (14FLA/mtr)?
100A
Raccoon City
Resident Evil
Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA
What is the recommended over current protection size?
40A/3P
In a 480V, 3 phase, 4w circuit, what is the phase-to-neutral voltage?
277V
A 100A feeder needs to be upsized from a #3 to a #1for voltage drop. What size should the ground wire be upsized to?
#4
Arrakis
Dune
Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA
What is the largest breaker size that can be used per code?
60A/3P
How many conductors should there be in a 3 phase, 4 wire, circuit? Name them all
5 (3 phase, 1 neutral, 1 ground)
What ampacity should the supply for a 480V, 3ph AHU/RTU with (4) 15HP motors (21FLA/mtr) and 50kW of electric heat?
(Bonus points for wire and conduit sizes)
150A (wire size – 3#1/0,#6G,2”C)
Duloc
Shrek
Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA
If the largest breaker size is to be used, what size should the phase conductors be? Bonus points for the ground wire size.
#10 AWG (motor feeder conductor sizes are not based off the breaker size.)
#10G AWG (NEC 250.122(A) – “…The equipment grounding conductor shall not be required to be larger than the circuit conductor suppliying the equipment.”…
In a 208Y, 3ph, 4w circuit with 10A on each phase conductor, how many amps should be on the neutral conductor?
0 (this is why we do not pull neutral conductors to balanced 3-phase circuits like dedicated motors.)
What size breaker should be given to a 208V, single phase electric water heater with (2) non-simultaneous 10kW heating elements?