Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA

What is the recommended quantity and size of the phase conductors?

#10AWG (NEC 430.22)

100

In a 208V, 3 phase circuit, what is the phase-to-phase voltage?

208V

100

What size breaker should the main of a 480V, 3ph, 1250kW, .8pf generator be?

2000A

100

Hoth

Star Wars The Empire Strikes Back

200

Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA

What table do I used to size the ground wire for the motor feeder?

Table 250.122 (NEC 250.122(D))

200

In a 3-phase, 4w system what should the ideal neutral-to-ground voltage be?

0V

200

What size breaker should supply a 480V, 3ph AHU/RTU with (6) 10HP motors (14FLA/mtr)?

100A

200

Raccoon City

Resident Evil

300

Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA

What is the recommended over current protection size?

40A/3P

300

In a 480V, 3 phase, 4w circuit, what is the phase-to-neutral voltage?

277V

300

A 100A feeder needs to be upsized from a #3 to a #1for voltage drop.  What size should the ground wire be upsized to?

 

#4

300

Arrakis

Dune

400

Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA

What is the largest breaker size that can be used per code?

60A/3P

400

How many conductors should there be in a 3 phase, 4 wire, circuit? Name them all

5 (3 phase, 1 neutral, 1 ground)

400

What ampacity should the supply for a 480V, 3ph AHU/RTU with (4) 15HP motors (21FLA/mtr) and 50kW of electric heat?

(Bonus points for wire and conduit sizes)

150A (wire size – 3#1/0,#6G,2”C)

400

Duloc

Shrek

500

Motor Info - single, continuous duty 15HP, 480V, 3ph motor with 21FLA

If the largest breaker size is to be used, what size should the phase conductors be? Bonus points for the ground wire size.

#10 AWG (motor feeder conductor sizes are not based off the breaker size.)

#10G AWG (NEC 250.122(A) – “…The equipment grounding conductor shall not be required to be larger than the circuit conductor suppliying the equipment.”…

500

In a 208Y, 3ph, 4w circuit with 10A on each phase conductor, how many amps should be on the neutral conductor?

0 (this is why we do not pull neutral conductors to balanced 3-phase circuits like dedicated motors.)

500

What size breaker should be given to a 208V, single phase electric water heater with (2) non-simultaneous 10kW heating elements?

60A

500