Name the code section that requires kitchen counter outlets to be GFCI protected?
210.08(A)6)
Type MC cable must be supported a minimum of every ____ feet?
6
The 2 main parts comprising a transformer is the _____ & _______?
coils and cores
A concrete encased electrode shall have a bare copper grounding electrode conductor not smaller than #___ AWG?
4
A transformer with 7,200 volts incoming has 720 windings on the primary side. The secondary voltage is 240 volts. How many windings are on the secondary side of the transformer?
24
Name the code table that says how deep conduits must be buried?
300.5
Romex must be supported at least every ____ feet?
4.5
The paper used in transformers has epoxy where?
on both sides of the paper
A ___-_____-_____ meter is connected to the incoming cables from the power company?
kilo-watt-hour
watt-hour
The minimum size copper equipment grounding conductor required for a 350 amp circuit is #______?
#3
Name the code table that says you can put a 15 amp rated receptacle on a 20 amp rated branch circuit?
Table 210.21(B)3)
The takeup for bending a 1/2" rigid 90 is _____ inches?
6
Oil in a transformer is primarily used for _____&______?
insulation & cooling
In a single family home, the grounding electrode conductor is connected from the meter base system neutral conductor to the ______ ______?
grounding rods
ground rods
What is the maximum number of #14 conductor allowances you can have in a 26 cubic inch junction box?
13
Name the code section that says receptacle outlets in a dwelling unit must be spaced no more than 12 feet apart and 6 feet within each doorway?
210.52(A)1)
EMT conduit must be supported within ____ inches of every outlet or junction box?
36
A multitap transformer is a transformer that provides options to connect to multiple _______?
voltages
There are ten 400-watt lights on a circuit with a voltage of 208 volts. What size breaker is required for this circuit?
25 amps
A 277 volt lighting circuit has nine 400 watt lights. What is the minimum size THHN conductor allowed?
#12
Name the code section that requires unused openings in electrical boxes to be effectively closed?
110.12(A)
314.17(A)
Conduits containing conductors size #4 or larger must be provided with _______ _______?
plastic bushings
The number of windings a transformer's primary side has in relation to the number of windings on the secondary side is called the ______?
ratio
_____ is not an acceptable method of connection for the grounding and bonding of equipment?
solder
What is the ampacity of a #12 THWN installed indoors with an ambient temperature of 116 degrees F?
18.75 amps