Emergency Lighting Equipment
Standby Generators
Batteries
UPS
100

Most emergency lighting is the form of __________ __________

Unit Equipment 

100

Provide a common area that would need a standby generator 

Hospital, shopping mall, jail, airport

100

which PPE should be worn when adding water to a wet cell battery? (3 items)

Rubber gloves, rubber apron, safety goggles and or face sheild 

100

Identify Common applications for UPSs 

Open ended question 

process control, computers/IT, gas monitoring equipment, security systems, emergency lighting.....

200

Common Battery voltages for Unit equipment are 

1.

2.

3.


6V

12V

24V

200

What is the purpose of the transfer switch in this circuit:

Ensure the generator does not back feed the utility 

200

Why does the average battery have a reduced output in the cold

The cold slows the chemical reaction 

200

What 2 actions does a UPS offer an electrical system?

1. provides backup power in the event of a utility failure

2. enhances the quality of the utility power to the connected loads (limits surges and noise)

300

How are the DC lamps of Unit Equipment tested?

Toggle the "Test Switch" 

300

Which component of a generator controls the engine speed under varying loads

Governor 

300

Which acid is found in the electrolyte of a Lead-Acid Battery?

Sulphuric Acid 

300

When an UPS is said to be in Off-Line Mode, the inverter is bypassed?

True 

400

According to the CEC, what is the maximum voltage drop permitted at a remote lamp when fed from Unit Equipment.  Provide the rule number as well 

5%

46-306-1

400

An emergency generator in a Class A facility must have how many Hours of fuel on site

72 hours 

400

For normal charging, a 12V battery would require a charging voltage an over voltage range of about 10% to ___%

20%

400

Identify the 3 essential components of any UPS systems

1. Batteries

2. Rectifier

3. Inverter 

500

According to the CEC, what is the minimum height from the finished floor that Unit Equipment can be mounted?  Also provide the rule number 

2 meters 

46-302 

500

according to CEC, an Automatic Transfer Switch servicing low-voltage essential electrical systems must be _________ operated, and _________ held.  Include the code rule

electrically 

mechanically

24-304-2-a,b 

500

Define the "Initial Charge" of a battery 

the charging process conducted after the battery is initially filled with electrolyte solution 

500

Which 2 types of batteries are the most common in a UPS system?

Lead-Acid 

Nickel-Cadmium 

600

Identify all 6 of the components commonly found in emergency lighting "Unit Equipment"

Rechargable Battery, battery trickle charger, battery voltage indicating light, test switch, transfer relay, one or more lamps 

600

Referring to the schematic below, the system is designed so that EG1 starts and takes the priority #1 loads first?

No, when utility power is lost, the generators all start automatically, the first generator to reach rated output will be connected to the bus and transfer current through the ATS-1 to priority #1 loads.  As each generator reaches output, they are added to the bus and ATS-2 passes current to the next most critical loads  

600

What is the purpose of D1,D2,D3 and D4

Form a full wave bridge rectifier - converts AC to DC

600

What is the semi-conductor component used to provide surge protection in a UPS

Metal Oxide varistor 

700

According to the CEC, if there is a requirement in a given area for emergency lighting, does an Exit Sign in this area need to be illuminated by an emergency power supply? Provide the rule number as well 

Yes

46-400-3

700

According to the CEC, if a Generator is used as the emergency power supply, which 3 parameters must be met? Provide the Code Rule(s) as well 

1. has sufficient capacity to handle the connected load(s)

2. will start and take the load automatically via a ATS

3. conforms with CSA C282 

46-202-3-a,b,c 

700

What is the purpose of SCR1?

Controls the conduction angle for current to the battery

700

With an "Off-Line" UPS, what happens when the AC Supply is lost?

Static Transfer Switch switches to the Battery circuit to maintain power to the critical loads 