Article 352
PVC
Article 350 and 356
LFMC and LFNC
Article 348
FMC
Article 386
Surface Metallic Raceways
Article 392
Cable Trays
200

PVC conduit shall be securely fastened within _____ in. of each box.

36

352.30(A)

200

_____ is a raceway of circular cross section having an outer liquidtight, nonmetallic, sunlight-resistant jacket over an inner flexible metal core.

LFMC

350.2 Liquidtight Flexible Metal Conduit (LFMC)

200

Article 348 covers the use, installation, and construction specifications for flexible metal conduit (FMC) and associated _____.

fittings 

348.1

200

The voltage between conductors in a surface metal raceway shall not exceed _____ unless the metal has a thickness of not less than 0.040 in. nominal.

300V 

386.12(2)

200

A cable tray is a unit or assembly of units or sections and associated fittings forming a _____ system used to securely fasten or support cables and raceways.

structural 

392.2 Cable Tray System

400

PVC conduit is permitted in locations subject to severe corrosive influences and where subject to chemicals for which the materials are specifically _____.

approved

352.10(B)

400

Extreme cold can cause some types of nonmetallic conduits to become _____ and therefore more susceptible to damage from physical contact.

brittle

356.10 Informational Note

400

Bends in FMC shall be made so that the conduit is not damaged and the internal diameter of the conduit is _____.

not effectively reduced 

348.24

400

Unbroken lengths of surface metal raceways can be run through dry _____.

walls, partitions, floors 

386.10(4)

400

For raceways terminating at a cable tray, a(an) _____ cable tray clamp or adapter shall be used to securely fasten the raceway to the cable tray system.

listed 

392.18(G)

600

Joints between PVC conduit, couplings, fittings, and boxes shall be made by _____.

an approved method 

352.48

600

LFNC shall be permitted for _____.

direct burial where listed and marked for the purpose, exposed work, outdoors where listed and marked for this purpose 

356.10(3) and (4)

600

Cable ties used to securely fasten flexible metal conduit shall be _____ for securement and support

listed and identified 

348.30(A)

600

Surface metal raceway enclosures providing a transition from other wiring methods shall have a means for connecting a(an) _____ conductor.

equipment grounding 

386.60

600

In industrial facilities where conditions of maintenance and supervision ensure that only qualified persons will service the installation, cable tray systems can be used to support _____.

raceways, cables, boxes and conduit bodies 

392.18(G)

800

The number of conductors permitted in PVC conduit shall not exceed the percentage fill specified in _____.

Chapter 9, Table 1 

352.22

800

Where flexibility is not required after installation, liquidtight flexible metal conduit shall be permitted to be used as an equipment grounding conductor when installed in accordance with _____.

250.118(6) 

350.60

800

Cut ends of FMC shall be trimmed or otherwise finished to remove rough edges, except where fittings _____.

thread into the convolutions 

348.28

800

The conductors, including splices and taps, in a metal surface raceway having a removable cover shall not fill the raceway to more than _____ percent of its cross-sectional area at the point of the splice or tap.

75%

386.56

800

Where single conductor cables comprising each phase, neutral, or grounded conductor of a circuit are connected in parallel in a cable tray, the conductors shall be installed _____, to prevent current imbalance in the paralleled conductors due to inductive reactance.

in groups consisting of not more than one conductor per phase, neutral, or grounded conductor 

392.20(C)

1000

Field bends in PVC conduit shall be made only _____.

with bending equipment identified for the purpose 

352.24

1000

When LFMC is used to connect equipment where flexibility is necessary to minimize the transmission of vibration from equipment or for equipment requiring movement after installation, a(an) _____ conductor shall be installed.

equipment grounding

350.60

1000

FMC shall not be installed _____.

in wet locations, embedded in poured concrete, where subject to physical damage 

348.12(1), (6), and (7)

1000

The ampacity adjustment factors of 310.15(C)(1) shall not apply to conductors installed in surface metal raceways where the _____.

cross-sectional area exceeds 4 sq in., current-carrying conductors do not exceed 30 in number, total cross-sectional area of all conductors does not exceed 20 percent of the interior cross-sectional area of the raceway 

386.22(1), (2), and (3)

1000

Cable _____ made and insulated by approved methods can be located within a cable tray provided they are accessible, and do not project above the side rails where the splices are subject to physical damage.

splices 

392.56