Article 90-110
Article 200-215
Article 220-230
Article 240-250
Article 300
200

When the Code uses "_____," it means the identified actions are allowed but not required, and they may be options or alternative methods.

shall be permitted 

90.5(B)

200

The insulated grounded conductor(s) in a multiconductor cable _____ AWG or larger, shall be permitted to be re-identified at the time of installation at its terminations.

4

200.6(E), 200.6(B)(4)

200

Service-drop conductors shall have _____.

sufficient ampacity to carry the load and adequate mechanical strength 

230.23(A)

200

Overcurrent protection for conductors and equipment is provided to _____ the circuit if the current reaches a value that will cause an excessive or dangerous temperature in conductors or conductor insulation.

open 

240.1 Informational Note

200

Cables laid in wood notches require protection against nails or screws by using a steel plate at least _____ in. thick, installed before the building finish is applied

1/16 

300.4(A)(2)

400

The manufacturer's name, trademark, or other descriptive markings by which the organization responsible for the product can be identified shall be _____.

placed on all electrical equipment 

110.21(A)(1)

400

Receptacle outlets installed on or above countertop or work surfaces shall be located not more than _____ in. above the countertop or worksurface.

20

210.52(C)(3)(1)

400

Service conductors supplying a building or other structure shall not _____ of another building or other structure.

pass through the interior 

230.3

400

_____ on equipment to be grounded shall be removed from contact surfaces to ensure good electrical continuity.

 Paint, Lacquer, or Enamel

250.12

400

Where direct-buried conductors and cables emerge from grade, they shall be protected by enclosures or raceways to a point at least _____ above finished grade

8 ft 

300.5(D)(1)

600

"Underground service conductors" are the underground conductors between the service point and the first point of connection to the service-entrance conductors in a terminal box, meter, or other enclosure, _____ the building wall.

inside or outside 

100 DEF Service Conductors, Underground

600

A meeting room with any floor dimension that is _____ ft or greater in any direction and that has a floor area of at least 215 sq ft shall have at least one floor receptacle outlet.

12 

210.65(B)(2)

600

Under the optional method for calculating a single-family dwelling service, general loads beyond the initial 10 kVA are assessed at a _____ percent demand factor.

40

220.82(B)

600

A circuit breaker with a _____ rating, such as 120/240V or 277/480V can be used on a solidly grounded circuit where the nominal voltage of any conductor to ground does not exceed the lower of the two values, and the nominal voltage between any two conductors does not exceed the higher value.

slash

240.85 

600

Openings around electrical penetrations into or through fire-resistant-rated walls, partitions, floors, or ceilings shall _____ to maintain the fire-resistance rating.

be firestopped using approved methods 

300.21

800

Tightening torque values for terminal connections shall be as indicated on equipment or in installation instructions provided by the manufacturer. An approved means shall be used to achieve the _____ torque value.

indicated 

110.14(D)

800

The required heating, air-conditioning, and refrigeration equipment receptacle outlet shall be located _____ the equipment.

on the same level as 

210.63(A)

800

For all other installations, the feeder or branch-circuit disconnecting means shall have a rating of not less than _____.

60A

225.39(D) 

800

Grounded electrical systems shall be connected to earth in a manner that will _____.

limit voltages due to lightning, line surges, or unintentional contact with higher-voltage lines and stabilize the voltage-to-ground during normal operation 

250.4(A)(1)

800

Equipment and devices shall only be permitted within ducts or plenum chambers specifically fabricated to transport environmental air if necessary for their direct action upon, or sensing of, the _____.

contained air 

300.22(B)

1000

The working space in front of the electric equipment shall not be less than _____ in. wide, or the width of the equipment, whichever is greater.

30

110.26(A)(2)

1000

Branch circuits shall be rated in accordance with the maximum permitted ampere rating of the _____.

overcurrent device 

210.18

1000

A feeder or service supplying household electric ranges, wall-mounted ovens, counter-mounted cooking units, and electric dryers, where the maximum unbalanced load has been determined in accordance with Table 220.55 for ranges and Table 220.54 for dryers shall be permitted to have an additional demand factor of _____ percent applied.

70 

220.61(B)(1)

1000

Where service-entrance conductors are installed in parallel in two or more raceways or cables, the size of the grounded conductor in each raceway or cable shall be based on the total circular mil area of the parallel ungrounded service-entrance conductors in the raceway or cable, sized in accordance with 250.24(C)(1), but not smaller than _____ AWG.

1/0

250.24(C)(2)

1000

Where raceways contain 4 AWG or larger insulated circuit conductors entering a cabinet, box, enclosure, or raceway, the conductors shall be protected by _____.

an identified fitting that provides a smooth rounded insulating surface, a listed metal fitting that has smooth rounded edges, threaded hubs that provide a smooth rounded or flared entry.

300.4(G)(1),(2), and (4)