FIRE TIME
FIRE LENGTH
FIRE DEVICES
PEOPLE ON FIRE
UNWANTED FIRE
100

This is how often smoke detectors must be tested.

What is annually?

100

This is the maximum height for the operating handle of a manual fire alarm box measured vertically from the floor.

What is 48 inches?

100

This is the color that manual fire boxes must be.

What is red?

100

This is the person responsible for the development of fire alarm and signaling system plans and specifications according to code.

What is System Designer? 

100

This is any alarm that occurs that is not the result of a potentially hazardous condition.

What is unwanted alarm?

200

This is the maximum time limit for a sprinkler water flow alarm for a water flow equal to or greater than that from the smallest orifice in the sprinkler system.

What is 90 seconds?

200

This is the maximum distance between visible appliances in a corridor.

What is 100 feet?

200

This is the minimum sound level for audible notification appliances in a sleeping area.

What is 75 Decibels. 

200

This is the individual who performs procedures used to determine the status of a system as intended by conducting acceptance, reacceptance, or physical checks on systems.

What is testing personnel?

200

This is an unwanted activation of an alarm initiating device caused by a person acting without malice.

What is unintentional alarm?

300

This is the time limit within which trouble signals must be restored.

What is 200 seconds?

300

This is the maximum distance from a sprinkler head to a heat detector being used for elevator recall.

What is 24 inches?

300

This is a public emergency alarm reporting system.

What is municipal fire alarm system.

300

This is the person who will conduct a visual examination of a system or portion thereof to verify that it appears to be in operating condition, in proper location, and free of physical damage or conditions that impair operation.  

What is inspection personnel?

300

This an unwanted activation of a signaling system or alarm initiation device in response to a stimulus or condition that is not the result of a potentially hazardous condition.

What is nuisance alarm?

400

This is the time limit for secondary power to turn on after loss of the primary power.

What is 10 seconds?

400

This is how far an ionization detector without silencing means should be places from a cooking appliance or heat source.

What is 20 Feet?

400

This is a signal initiated by the fire alarm system or device indicative of a fault in a monitored circuit or component.

What is trouble signal.

400

This is the individual responsible for the proper installation of fire alarm and signaling systems in accordance with plans, specifications, and manufacturers requirements. 

What is installation personnel?

400

This is an unwanted activation of an alarm initiating device caused by a person acting with malice.

What is malicious alarm?

500

This is the maximum air sample transport time from the farthest port to the detector for an air sampling smoke detector.

What is 120 seconds?

500

This is the maximum slope for a ceiling that is considered to be level.

What is 1.5 inches per foot.

500

This is a condition which occurs when air containing smoke particles or gaseous combustion products is heated by smoldering or burning material and rises until reaches a level at which there is no longer a difference in temperature between it and the surrounding air.

What is stratification? 

500

This is the individual who will perform procedures, adjustments, replacement of components, system programming, and maintenance as described in the manufacturers service instructions that can affect any aspect of the performance of the system.

What is service personnel?

500

This is an unwanted activation of an alarm initiating device or system output function where the cause has not been identified.

What is unknown alarm?