Conductors & Circuits
Fire Alarm Equipment
Special Systems
Locations & Conditions
Extra Knowledge
200

Circuit class with short circuit protection.

What is Class X?

200

Color required for the primary disconnecting means.

What is red

200

: Mass notification system requirements are in the NFPA 72,  Chapter __.

What is 24?

200

Area on the side of a building is considered a __ location.

What is wet?

200

Firestopping material for dynamic penetrations like wireways.

What are pillows?

400

Which circuit type uses digital addressable communication?

What is SLC?

400

Smoke detectors may be installed in elevator hoistways only when __.

What is hoistway is sprinklered?

400

Supervising station originally operated by municipal fire departments.

What is remote station?

400

Which area does NOT require intelligible signal?

What is mechanical room?

400

Failure to de-burr conduit often results in __.

What is ground faults?

600

HVAC systems over __ CFM require shutdown during fire alarm

What is 2000 CFM

600

The entity responsible for developing “red line drawings.”

What is the installer?

600

Level __ survivability requires full sprinklers.

What is Level 3

600

Carbon monoxide detectors must be installed outside sleeping areas within __ feet of bedroom doors.

What is 21 feet

600

Blueprint paper is coated with which two chemicals?

What are ferric ammonium citrate & potassium ferricyanide?

800

An ECS must operate for 24 hrs standby, then __ full operation.

What is 2 hours?

800

: After inspection or test, who completes the Record of Inspection and Test?

What is the installer?

800

Kitchen hood actuation in a protected premises must cause this signal.

What is alarm?

800

Minimum sound pressure level required for private mode signaling in the given example.

What is 67 dBA?

800

NEC 760.3(B) references which section for ducts & plenums?

What is 300.22?

1000

Max loop resistance is 75 Ohms. With 18 AWG copper, max length is __.

What is 4641 feet?

1000

The process by which contractor designs and installs systems.

What is design/build?

1000

Substitute cable for Type FPLR.

What is FPLP?

1000

Carbon monoxide detector requirements are in NFPA 72 but were once in NFPA __.

What is 720

1000

Max number of initiating devices interconnected when monitored for integrity.

What is 64?