O2
DRAFT
PARTS OF A HEATER
DAMPER OR REGISTER
BACK THAT GAS UP
BAD "DAD" JOKES
200

This controls the amount of excess O2 in a heater

Air Registers

200

This helps control draft on a heater

Damper

200

These are the 3 major sections of a vertical, cylindrical heater

Radiant section, convection section, stack

200

Draft is on target but O2 is below target

Open air regiser

200

This is produced due to incomplete combustion

Carbon Monoxide

200

What did the buffalo say to his son when he dropped him off at school?

Bison

400

Air entering the heater and not taking part of combustion is called this

Tramp air

400

Flue gas is removed from the heater through this heater part that usually has strakes

The stack

400

In general, ~2/3 of the heat transfer occurs in this secion

Radiant section

400

Draft is higher than normal and O2 is lower than normal

Open air register

400

Natural gas is an odorless, gaseous mixture of hydrocarbons, predominantly made up of this

Methane

400

What do you call a bear with no teeth?

Gummy bear

600

The percent of total air supplied that is more than what is required for Stoichiometric combustion 

Excess air

600

While an induced draft heater is not common in refining, these other three styles are

Natural draft, balanced draft, and forced draft

600

The purpose of this section in a Natural draft heater is to recover heat to increase the heater's overall efficiency

Convection section

600

Draft and air are both lower than normal

Open damper

600

SO2 and NOx are extremely reactive and decomposes in contact with water, oxygen, and other chemicals to form this

Acid rain

600

This is a typical dad response when asked if he got a haircut

I got them all cut or no, I got my ears lowered

800

Elevated levels of excess air increases fuel consumption and increases this, an essential component of air pollution

NOx

800

This controls the excess air for a forced draft heater

Forced draft blower, fan louvers or combustion air dampers

800

The lower 2-3 rows of convection section tubes, known as these, receive a significant amount of radiation heat transfer

Shock or Shield tubes

800

Draft is higher than normal and O2 is on the high side of normal

Close damper

800

Operating above or below this will trip the fuel gas on your heater

Pressure

800

The place that Dads say that people are dying to get in 

Cemetery

1000

Operating with insufficient excess air may generate levels of CO and this which is required for a fuel rich firebox

Combustables or unburned fuel

1000

This is considered the most efficient draft style of heater

Balanced draft

1000

This burner type uses recirculation to help reduce NOx

Low NOx burner

1000

Your O2 reading is 1%

Nothing. Air hold. Slowly cut fuel gas 10% of flow per minutes if override hasn't activated. Let operators know to stay away from the heater

1000

The three T's of combustion are Time, Turbulence, and this....is it hot in here?

Temperature

1000

How are the movies Titanic and The Sixth Sense the same?

ICY ( I see) dead people

M