F
F
F
FF
F
100

Explain the different types of fires extinguishers and what type of fires they are used for. Which types do we have at IAD51?

Class A – Ordinary Combustibles

Solids, not metal

Class B – Flammable Liquids or Gases

Grease, tar, alcohols, flammable gas

Class C – Electrical

Energized equipment

Class D – Metal

Magnesium, titanium, sodium

Class K – Cooking Oils

Animal and vegetable oils, fats

100

Define and describe the basic functions of each of the major components in the fire system. Express where each can be found on site.

a. FACP

Fire Alarm Control Panel

Central information hub for alarms/notifications

The main FACP that has all the building alarms/notifications are in the lobby

The data hall FACP has all the alarms/notifications for that suite

b. NAC Panel

Notification Appliance Card Panel

Communication circuit that performs the preset functions of the fire system

These are the red boxes on the wall around the building

c. NICs

Network Interface Cards

Ties the sensing devices to the network

Located inside the FACP

d. Annunciator System

Visual and audible devices to provide warnings and/or alerts

e. Speaker/Strobe

The instruments which provides the noise and light indication upon activation of fire alarm

i. Sprinkler head:

detects fire

j. pre action cabinet:

uses closed sprinkler heads that will break upon high temperature.

two steps of activation: mechanical and electrical.

k. Vesda:

Very early smoke detection apparatus

triggers supervisory

orange pipes draw in air samples to detect smoke

f. Pull Station

Manual operation of the fire alarm

g. Smoke Detector

Detects smoke and provides supervisory signal upon activation

h. Flame Detector

Monitors arc flashes from explosion

In generator enclosures


100

Explain the primary and secondary functions of the electric room dampers. What is their failed position?

Should a UPS CRAC fail, the primary function is to provide cooling from the neighboring UPS rooms

As the dampers failure position is to shut, the secondary function is to prevent fire/smoke to neighboring UPS rooms.

100

Describe the water flow path through the fire system.

Utility water -> Water Entry Room -> Fire Riser -> Pre-Action Cabinets -> Sprinklers

200

Describe Wet and Dry systems and include the typical locations each of them.

a. wet systems

Pipes are filled with water

Discharges immediately when sprinkler head is broken

PBB spaces

b. Dry Systems

Pipes filled with pressurized air

When sprinkler head is broken, air is discharged, valve trips and water flows into the piping

Used in spaces that are prone to freezing (loading dock, attics, parking garages)

200

Explain the primary and secondary functions of the electric room dampers. What is their failed position?

Should a UPS CRAC fail, the primary function is to provide cooling from the neighboring UPS rooms

As the dampers failure position is to shut, the secondary function is to prevent fire/smoke to neighboring UPS rooms.

200

Explain the purpose of using Nitrogen in the fire system, and at what point during the sequence is it utilized.

To prevent corrosion within the piping

Before water flow, used to clear oxygen from the pipes

300

Explain the Pre-Action system to include:

a. Function

pre-action systems hold water back until a fire is detected and confirmed

b. Sequence of Operation

Two steps of activation: mechanical (loss of air pressure) and electrical (cross-detection)

c. Power Supply

Dual-fed from GPNL-2

300

Explain the following conditions. Include when each condition can be reset on the FACP.

a. Trouble

Malfunctions that can prevent proper operation

Clears automatically once the condition no longer exists

b. Supervisory

A change of operational state in a piece of equipment, system or process

Clears when condition is back into normal operation

c. Alarm

Detected alarm condition from component

Clears only by the Fire Department

300

Describe a Hot Work Permit, to include:

a. Responsible Party

Operations team – fills out permit, distributes to vendor, and collects upon work completion

b. Required Information

Name of contractor, date, change request #, location of work, what work is performed, parties involved, signature

c. When they are needed

before any temporary operation involving open flames or producing heat and/or sparks, such as welding, cutting, brazing, or grinding, can begin

300

Describe the basic sequence of operation of a Dual-Action Fire System.

1. ELECTRICAL – Cross-Detection:

Two smoke detectors activated within

the same zone (cross-detection)

 the solenoid valve will open, releasing

water pressure from the priming

chamber

• Note that the deluge valve will not

open

2. MECHANICAL - Loss of air pressure:

Opening of an automatic sprinkler via

breaking or sprinkler head (155-

165˚F) activates the low air supervisory

switch

 Note that the water will not enter the

system piping.

1&2: Activation of the detection condition AND the opening of an automatic sprinkler…

deluge valve to open and water will flow out of any open sprinklers.

the alarm pressure switch will also activate.

400

Describe the basic functions of each of the major components in a Pre-Action Cabinet. -Gauges 

System Air Pressure - measures the pressure of the dry piping that feeds to the sprinkler heads

dropping below 12 psi triggers a supervisory

Priming Pressure - measures the water pressure that is closing the Deluge valve

should be equal to or greater than the water supply pressure

Water Supply Pressure – measures the incoming water pressure from the Water Entry Room

closed off from the Deluge valve cover

400

Describe the basic functions of each of the major components in a Pre-Action Cabinet. -Nitrogen system and air compressor


c. Nitrogen System

Supplies nitrogen to the dry pipes

Ensures oxygen and moisture is displaced in piping

d. Air Compressor

Pushes nitrogen to the dry pipes

Turns on when System Air Pressure drops below 10 psi

Will turn off when it reaches 20 psi

400

Describe a Red E-tag, to include:

a. Purpose

To ensure insurance coverage upon impairments monitored by the fire system

b. Required information

Location info (name, address, etc.)

Fire protection Info (type, equipment, area)

Impairment info (reason, start/end date)

c. Insurance Company Name

FM Global

d. When they are needed

When an impairment of the fire system is made



400

Explain VESDAs to include:

a. Sequence of operation

Orange pipes draw in air samples, passing thru filters to clear any debris

Air then passes thru laser chamber which detects if smoke is present

b. Power supply

GPNL2

c. System response to VESDA alarm

Supervisory to the FACP

400

Describe the basic functions of each of the major components in a Pre-Action Cabinet. -Valves 

Solenoid valve

Releases priming pressure

Activated during cross-detection

Deluge Valve

Held closed by the priming pressure

Allows water to the sprinkler piping once both conditions are met (cross-detection, loss of air pressure)

Shut-off Valve

Used for testing the system

Water Supply Control Valve

Manually shuts off the pre-action system by preventing water flow

M
e
n
u