Your over current device is set at 60 amps. What is the minimum sized Equipment ground required in Cu?
Table 250.122
#10
What is the scope of Article 200?
This article provides requirements for the following:
What conditions must be met to be able to use Flexible metallic conduit as an equipment ground.
Your over current device is set at 100 amps. What is the minimum sized Equipment ground required in Cu?
Table 250.122
#8
200.2(B)
The continuity of a grounded conductor shall not depend on a metallic connection to a metallic enclosure, raceway or cable armor.
Give an example.
Grounded conductors in a service panel cannot be terminated onto ground bars. They must be terminated onto a neutral bar.
What conditions must be met to be able to use Liquid tight Flexible metallic conduit as an equipment ground?
Your over current device is set at 200 amps. What is the minimum sized Equipment ground required in Cu?
Table 250.122
#6
Explain 200.4(B)
When you have multiple circuits and multiple neutrals coming out of one conduit you need to identify which neutral belongs to which circuit with a zip tie.
(preferred)
On the board, draw a sketch of a riser diagram with an underground meter base, service disconnect and main lug panel. Highlight where the EGC is located.
The Equipment ground will be located between the service disconnect and the main lug panel.
How should a Grounded conductor #6 or smaller be identified?
Explain the dangers of an un identified grounded conductor.
200.6
1-8
Typically we will use white tape.
Service rated wires will have the grounded conductor with a white stripe from the manufacturer.
Where a single equipment grounding conductor is run with multiple circuits in the same raceway, cable, or cable tray, it shall be sized for the _____ overcurrent device protecting conductors in the raceway, cable, or cable tray.
Give an example.
250.122 (C)
Shall be sized for the largest over current device protecting the conductors.
Neutral conductors shall not be used for more than one branch circuit, for more than one multiwire branch circuit, or for more than one set of ungrounded feeder conductors unless specifically permitted elsewhere in this Code.
Explain why this may be a safety hazard if this code is not followed.
Neutral conductors will not trip a breaker if they are overloaded. The wire may burn and cause harm to people or damage property.