Class 1
Class 2
Class 3
Commercial Garages / Airport Hangars
Motor Fuel Dispensing Facilities
100

Class 1, Division 1 and 2 locations exist where fire or explosion hazards may exist due to________________________.

Flammable gases or vapors or flammable liquids.


501.1

100

Class 2 Divisions 1 and 2 are locations where fire or explosion hazards may exist due to __________________.

Combustible Dust.


502.1

100

Class 3 Division 1 and 2 locations include locations where fire or explosion hazard exist due to __________________.

Ignitable fibers or flyings.

503.1

100

Parking garages used for parking or storage shall be ________________________.

Permitted to be unclassified. 


511.3(A)

100

This article shall apply to ________________________________________________________________________________.

Motor fuel dispensing facilities, marine / motor fuel dispensing facilities, motor fuel dispensing facilities located inside buildings, and fleet vehicle motor fuel dispensing facilities. 

514.1

200

Thickness if the sealing compound shall not be less than the trade size of the sealing fitting, however in no case shall it be less than __________.

5/8"

501.15(C)(3)

200

In Class 2, Division 1 and 2 locations, All boxes and fittings shall be ______________.

Dusttight.


502.10(B)(4)

200

Is liquidtight flexible metal conduit allowed in Class 3 Division 1 locations?

Yes, with listed fittings.


503.10(A)(3)

200

Underground wiring shall be installed in __________________________.

Threaded rigid metal conduit or intermediate metal conduit.

511.8

200

A class 1 Division 2 rating shall extend 18" vertically from the ground, and how far horizontally from a motor fuel dispensing device?

20'

Figure 514.3

300

Luminaires in Class 1 Division 1 locations shall be protected by ________________.

suitable guard or by location.


501.130(A)(2)

300

In Class2 Division 1 locations, switches, circuit breakers, motor controllers, fuses, pushbuttons, relays, and similar devices shall be provided with _________________.

Enclosures identified for that location.


502.115(A)

300

In class 3 locations, a luminaire exposed to physical damage shall be protected by _______________.

A suitable guard


503.130(B)

300

In an aircraft hangar, any pit or depression below the level of the hangar floor  shall be classified as ___________________.

Class 1 Division 1


513.3(A)

300
Fuel dispensing systems shall be provided with one or more clearly identified emergency shut-off devices or disconnects located no less than 20' but no more than __________ from the device they serve. 

100'

514.11(A)

400

Transformer windings, impedance coils, solenoids, and other windings that DO NOT incorporate sliding or make-or-break contacts shall be provided with enclosures.  __________________ enclosures shall be permitted.

General-purpose-type


501.105(B)(4)

400

In Class 2 Division 2, seals shall not be required to be ______________.

Explosionproof.


502.15(4)

400

Storage battery charging equipment shall be located in separate rooms built or lined with ________________________.

Substantial noncombustible materials.


503.160

400

In a minor repair garage, where Class 1 liquids are not transferred or dispensed, the entire space within any pit belowgrade work area that is not ventilated is classified as a __________________ location.

Class 1, Division 2 


Table 511.3(C)

400

All metal raceways, the metal armor or metallic sheath on cables, and all non-current carrying metal parts of fixed and portable electrical equipment, regardless of _____________ shall be grounded and bonded. 

Voltage


514.16

500

Receptacles in Class 1 Division 1 and 2 shall be part of the premises wiring except as permitted by _________________.

501.140(A)


501.145(A)

500

No transformer or capacitor shall be installed in a ______________________ location.

Class 2 Division 1 Group E


502.100(A)(3)

500

The _______________ and ______________ shall not be depended on for bonding purposes.

Locknut-bushing ; double locknut-bushing

500

Aircraft electrical systems shall be de-energized when the aircraft is _________________________.

Stored in a hangar and whenever possible, while undergoing maintenance. 

513.10(A)(1)

500

An overhead dispensing device is classified as a Class 1 Division 2 with 18" of the dispenser enclosure, extending horizontally in all directions down to _____________.

Grade level


Table 513(B)(1)