Directional Controls
Metering Logic
Field Procedures
The Coil Shuffle
Heating Essentials
100

Water temperatures leaving the water-heating loop are generally what temp?

No greater than 145°F.

100

A TXV adjusts the amount of liquid refrigerant traveling through it to maintain a consistent ______.

superheat

100

New systems come from the factory with the service valves in the closed position with the refrigerant locked in the

outdoor unit

100

Which terminal controls the reversing valve on most heat pumps?

: O/B terminal

100

Why do air-source heat pumps usually require auxiliary heat?

Because the heating capacity of the unit drops as house heating requirements increase.

200

What component is responsible for reversing the flow of refrigerant in a heat pump?

The reversing valve

200

Capillary tubing is commonly used as a metering device in split ac systems. (True or False)

False.

Window ac units

200

On a new system that has a service ball valve, the access port is used for pressure testing and vacuuming before turning the ball valve _____ and releasing the refrigerant into the rest of the system.

90°

200

The outdoor coil is the condenser in:

The cooling cycle.

200

What is auxiliary heat?

Another heat source added to make up the difference between the heat pump capacity and the house load

300

The internal piston in the reversing valve is moved from one side to the other by:

 Pressure difference.

300

What prevents the refrigerant from flowing through the outdoor metering device during the cooling cycle?

The outdoor check valve

300

What is the main difference between a heat pump and a fossil fuel furnace?

Heat pumps move heat instead of creating it.

300

The indoor coil is the condenser in:

The heating cycle.

300

What is the most common form of auxiliary heat used in heat pumps?

Electric resistance strip heat

400

What prevents the refrigerant from flowing through the indoor metering device during the heating cycle?

The indoor check valve

400

When is the indoor metering device bypassed?

The heating cycle

400

How can an air-source heat pump heat when the outdoor temperature is cold?

All molecules contain some heat until they reach absolute zero (-460°F).

400

The outdoor coil is the evaporator in:

The heating cycle.

400

Refrigerant is responsible for shifting the position of the sliding cylinder of the reversing valve? (true or False)

False 

Pressure

500

What is the purpose of the check valves that are installed in parallel with the metering devices on heat pumps?

To direct the flow of refrigerant around the metering device that is not being used

500

Why does a heat pump need two metering devices?

One metering device is used for the cooling cycle and one for the heating cycle.

500

When is the Y terminal energized on most heat pump thermostats?

Both first-stage heating and cooling

500

The indoor coil is the evaporator in:

The cooling cycle.

500

What makes the main valve in the reversing valve shift from one side to the other?

Pressure difference from one side of the valve to the other

M
e
n
u