WHIMIS
Air baby
Valves
HWH Piping systems
Components cont...
100

If a Hazardous material were to be transferred to a smaller approved container for ease of use on a jobsite what must be done?

What is,  A workplace label with the required safety data needs to be affixed to the new container?

100

The preferred location of an air separator ?

What is on the supply main closer to the boiler?


100

Required on all potable make up water lines ?

What is Backflow prevention

100

 Also known as the 1st fed 1st return system ?

What is a direct return system

100

Closely spaced tees create hydraulic separation between primary and secondary loops by limiting the ____  ____  between the tees?

What is Head loss / friction loss.

200

What characteristics of an impellor will increase the volume it can produce ?

What is the width of the impellor.

200

Requires 18" of straight horizontal pipe on the inlet side?

What is an Air scoop or Air purger.

200

Some make up water assembly's come with a feed valve that has a lever to quick fill the system. If not a bypass is recommended for this purpose. What device must not be bypassed?

what is the backflow preventer.

200

 What principal is the Diversion tee system based on?

What is Bernoulli's Principal (where velocity is greatest, pressure is least).

200

A piping arrangement that limits unwanted thermal migration (thermosiphoning) through a static hydronic loop?

What is a thermal trap.

300

Another name for 3 piece circulators  ?

What is Dry rotor pumps.

300

This device has disks swell up in the presence of water and shrink in the presence of air?

what is an automatic disc air vent.

300

This must be installed directly into every Boiler with no other valves between itself and the boiler ?

What is a pressure relief valve.

300

 A two pipe system that provides a well balanced system without the use of balance valves?

What is a Reverse return system.

300

Horizontal pipes that connect heat transfer units to a riser or the main ?

What is Runouts

400

A 20 psi closed hydronic systems circulation pump can create a 10 psi pressure differential. The expansion tank is located 1/2 way between the inlet and outlet of the pump. what is the inlet and outlet pressures when circulating ?

What is 15 psi at the inlet and 25 psi at its outlet.

400

Air is most easily removed from water where the temperature is hottest and the flow rate is _____? 

What is slowest"

400

A zone valve with 4 wires includes an end switch also known as a proving switch. What does this switch prove and why?

What is it proves the zone valve has fully opened so its safe to energize the pump via a relay.

400

What type of piping arrangement/configuration do most radiant in floor systems use?

What is the Home run distribution system

400

Sometimes called a spring piece this piping arrangement allows for expansion and contraction within the hydronic system??

What is a swing joint.

500

A 20 psi closed hydronic systems circulation pump can create a 10 psi pressure differential. The expansion tank is located 1/2 way between the inlet and outlet of the pump. what is the inlet and outlet pressures when static ?

What is 20psi .

500

Allows air in the top of a boiler to be routed to compression tank above the boiler rather than into the supply main ?

What is a Boiler fitting / Boiler tee

500

Can control the water temperature and flow rates both to the supply and return piping of the boiler ?

What is a four way mixing valve

500

 The term used to describe systems with multiple pumps that work independently of each other and thus do not affect each others performance ?

What is Hydraulic separation.

500

 Complete this statement," Balancing valves operate best between ___ ___ % open?

What is between 50 and 100 % open.