True or False
Charge
Extra
Word math
More math
100

You can charge liquid in the liquid line when the system is running

False

Pressure is too great on the high side when the system is running

100

Adding refrigerant to a system

What is charging

100

The scale of condensing and vaporizing temperatures for a zeotropic refrigerant blend

What is a temperature glide

100

Low pressures + high superheat + low subcooling 

 Low charge

100

 50oz of refrigerant converted to pounds

 3.125 pounds

[50\16=3.125]

200

When charging r-410a the jug is upright

False

up-side-down

200

Increased system temperatures and operating pressures

What does overcharging a system cause

200

Liquid line temperature - condenser saturation temperature 

 What is subcooling

200

Low suction pressure + normal to high head pressure+ low superheat + normal to high subcooling 

  Dirty evaporator coil\ reduced airflow

200

R-22 system

80* ambient temp

70psig, 230psig

SL 55*, LL 98*

What is the superheat and subcooling for this system? 

 70psig=40* evap. sat. temp

230psig=111* cond. sat. temp.

55-40=15* superheat

111-98=13* subcooling

300

You have to purge your gauge lines every time before you charge a system

True

Absolutely

300

Prevents liquid refrigerant from entering a system while charging

What is throttling or using a restrictor

300

 The position of the service valve to allow system operation

 What is back-seated

300

high pressures + low superheat + high subcooling 

 Overcharge

300

R-410a

Ambient 75*

100psig, 290psig

SL 50*    LL 107*

What is superheat and subcooling? 

 100psig=31* sat. temp.

290psig=94* sat. temp.

50-31=19* superheat

107-94=13* subcooling

400

An electronic charging scale and manufacturers charging chart is the most accurate way to charge a system

True

400

A special valve that keep refrigerant from entering a virgin refrigerant cylinder

What is a check valve

400

The position of the service valve used when the system is being pumped down 

 What is front-seated

(on the high side until refrigerant is backed into condenser, then suction line valve is front-seated as well to trap refrigerant in condenser coil)

400

Normal to low superheat + high saturation temperatures + high subcooling + higher than normal system pressures

 Dirty condenser coil

400

R410a

Ambient 90*

125psig, 350psig

SL 60*   LL 115*

What is superheat and subcooling? 

 125psig=43* evap. sat. temp.

350psig=107* cond. sat. temp.

60-43=17* superheat

115-107=8* subcooling

500

You can repair a system and not pressure test, change the drier or pull vacuum if you do it quickly on a dry day

FALSE

ALWAYS pressure test, change the drier and pull vacuum every time you open a system

500

Only Liquid

What is the fastest way to charge a refrigeration system

500

When you unscrew your service hose at the manifold long enough to get refrigerant out of the line 

 What is purging

500

Suction line temperature - evaporator saturation temperature 

 Superheat

500

R-22

Ambient 86*

74psig, 250psig 

 SL 55*   LL 120*

What is superheat and subcooling? 

 74psig=44* evap. sat. temp.

250psig=117* cond. sat. temp.

55-44=11* superheat

120-117=3* subcooling