HVAC
Refrigeration
EMS
Lighting
100

What is the lowest setting for cooling we can go for a sales floor RTU?

72 degrees is the lowest cool setting for sales floor RTUs we can adjust to

100

How do you terminate a defrost in Novar?

Adjust the termination temperature below what the current controlling sensor is reading for that circuit, and change it back it parameters once the defrost has been confirmed to have been terminated.

100

What does it mean when a module shows "Down" and highlighted yellow? (Opus)

This module is in comm loss

100

What does "Not Present" mean for an NCH-1000 breaker?

This means the breaker is not communicating and will not function with the schedule or remote commands.

200

What does a performance alert mean for an RTU? (Opus)

This means there is an issue with the unit and most likely will show an active alarm in the alarm tab for the unit.

200

Defrost points should be set to closed or open contacts? 

Defrosts should be set to Open

200

How do you attempt to reset a module for stale data/comm loss in Opus?

Change the module to False, ping the device three times and return the module to True when finished

200

What does a faulted NCH-1000 breaker mean?

This means the breaker is stuck either on or off and will not change its status until the fault has been cleared.

300

What does a MOD MAINT OVERRIDE mean in Novar?

This means the toggle switch for this asset is not in the auto position and being forced on site.

300

In Danfoss 800s, what is the difference when staging with unloaders? 

These are loaders in Danfoss 880s and will add MBTU/HP to your staging instead of reducing it as it normally does for other EMS systems.

300

How much VAC should a Lingo XE receive on the power terminals?

24 VAC

300

If a store has had a power outage and says the lights in the parking lot will not turn off, what should be the first thing you check? 

Check the astronomical clock and be sure they are aligned. The clocks not being aligned can cause the lighting to be stuck on/off since it will not know what the accurate time is. This is pretty typical to happen in Novar when a store loses power.

400

What does it mean when the auxiliary sensor is higher than the zone sensor with an active cooling stage?

This means the unit is not properly cooling and supplying warmer air than it should be and needs service. Possibly a sensor issue. A setpoint adjustment will not fix this.

400

What should we do when we receive a request for a staging issue in Copeland/CPC?

This will have to be addressed by Copeland support since we can not adjust staging in CPC. 

400

Does a cabling ticket need to be made when all RTUs are showing in comm loss?

No, this would not be a cabling ticket. This could mean there is a possible daisy chain issue with the wiring, a problem with the transition board, or an addressing issue.

400

Who should you include when you change the exterior lighting schedules in Novar when responding to the email?

Include Jacob and BPC email to the chain to have the changes be made permanent. Otherwise, this will revert back on Sunday when IoT automatically updates the schedules.

500

How do we access an XCM10 controller in Opus to view AHUs?

You will have to open a new station connection with the EMS link (ems09.s0XXXX.us.wal-mart.com) and login with your credentials.

500

What does it mean when all of the compressors on a rack are calling to be off, and you noticed the discharge pressure went into alarm above 350 psi the same day?

This means the rack locked out on high head pressure (a safety mechanism) and the high pressure lockout will need to be reset before the compressors will run.

500

What should the Vlan for most controllers be set to in a port?

Vlan should be set to 20 for most controllers

500

What will a Phase Loss alarm do to the lighting? 

Phase loss will force all of the exterior lighting on and shut off all of the RTUs. 

M
e
n
u