How much$ did I just throw out?
CODE(y)
What is this thinggy called?
NYSER DUH
Greenspark Poppuri
100

roll of 3/4" flex

189

100

The wire size and Breaker size we should use for a Tesla EV charger


(bonus 50 points to include Wallbox sizes, include neutral,EGC, hots)

what is 60A 2p w/ #6 wire #10 EGC


What is 50A 2p w/ #8 wire #10 EGC no Neutral needed

100

Pic #1

Wire loom

100

What's wrong with this pic

#1a / #1b

Wires landing at DC MPPT terminals is incomplete (not all strands land at terminals).

100

Who are the people in your chain of command

Who is my crew lead

Who is matt H

Who is Kerry/Skyler 

Order is important! Brad is also always all ears and can direct you if you need anything.

200

IR 14' rail

49.5

200

An unintentional, electrically conducting connection between an ungrounded conductor and the normally non-current carrying conductors, metallic enclosures etc. 

Ground fault

200

Pic #2

Connon ball/ Enphase end connector

200

Whats wrong with this pic

#2

Ungrounded conductor cannot be marked using white, gray, or white striped conductors to avoid confusion with grounded conductor markings

200

our resi sale goal for 2023 (# of jobs within 25)

 200-250

300

PV power source sticker

1.40

300

Define "straight Pull"

Define "U Pull"


bonus 100pts: What is the minimum box size for a straight pull. with a 3/4" emt and 1" emt entering one side and 1.5" emt coming out the opposite side. 

12x whatever x whatever


1.5*8=12


314.28A1

300

Pic #3

Jet Line/ Pull Rope/ 250' tape measure

300

Whats wrong with this pic

Grounded conductor is not properly identified as white or gray. 

Equipment grounding conductor (EGC) is not properly identified as either bare, green, or green with continuous yellow stripe(s).

300

name this core value:

Be forward thinking

Have Humility

Seek the greater good

Actions speak louder than words

Be a Leader

400

S clip

.21

400

What is the full load current of a 7.7 and a 3.0 kw inverter combined. 


What should the wire size and breaker size be for the output of the combined inverters

7.7+3.0KW = 10,700W

10,700W/240V=44.58A

44.58*1.25=55.729A

Round up tp nearest breaker size = 60A breaker

Wire size 6

400

Pic #4

MC4 or Enphase Ferrule


400

What's wrong with this pic

DC power source information label is missing, incomplete, or unsuitable for the environment. Label: OPERATING CURRENT____ OPERATING VOLTAGE____ MAXIMUM SYSTEM VOLTAGE____ SHORT CIRCUIT CURRENT____

500

UFO clamp W/ end

3.13

500

tell me about OHMS law!

If you know 2of the three values you can figure out the third. 

V=I*R

I=V/R

R=E/I

500

Pic #5

N3

Fused 

60a simgle phase disco

500

What's wrong with this pic

PV backfeed breacker PV disconnect label not located adjacent to circuit breaker Per NEC 705.12 (D)(2)(3)(b