These are the types of equipment that the UCC is compatible with
What is HC and HP, up to 4 stages of compressor
This is the outdoor sensor for the UCC, that can measure temperature and humidity
What is the UCC-OTH
(T/F?), the UCC accounts for daylight savings
What is true?
(T/F?), an outdoor sensor is necessary for economizer function
What is true?
This is the protocol that the UCC can use to communicate to other devices
What is Modbus?
This sensor reads indoor temperature and humidity, and also has a display to allow some control to the main UCC unit
What is the UCC-DTH?
This is the amount of daily start and stop events a user can program
What is 2 start, 2 stop?
Two of these dampers must be used with the UCC when it is acting as an economizer
This is the amount of auxiliary outputs in the UCC
What is 3? (2x 0-1V, 1x SPDT relay)
These sensors can be used for indoor temperature reading and averaging
What are T-S1 and T-S2?
This is the amount of unique holiday events that can be scheduled in the UCC
What is 30?
This is the position of the economizer dampers when outside air is not suitable for cooling
What is closed/0V? (if daytime ventilation is enabled, may go to a minimum open position)
This is the default PIN to access the installer options
What is 032? (can be adjusted by installer)
This iO HVAC product can be tied into the UCC to help with the ventilation function
What is the CO2-TH?
This is the feature that temporarily overrides setback temperatures in the UCC
What is the after-hours timer?
What is false?