228 RW
Question #1
30amps
408.36(A)
228.1
Question #4
Thermoset
400.4 (table)
228.2
Question #3
12"-3"= 9"
404.3
312.6 (B) Table Note #2
228.3
Question #26
8'
410.10(D)(1)
228.4
Question #3
12500/240 = 52amps
52 x 125% = 65a - 6awg
228 RW
Question #12
Correctional Facilities
406.12
228.1
Question #1
400.12
228.2
Question #6
300v
404.8(B)
228.3
Question #7
410.10(D)
228.4
Question #24
(8200/240) x (125%) = 42.71 or 43amps - 8awg
228 RW
Question #10
1/2"
410.116(A)(1)
228.1
Question #7
Section 400.5
228.2
Question #9
1 hot / 1 neutral / 1 egc / 1 iso grnd = 4
406.3 (E)
228.3
Question #1
3"
410.116(B)
228.4
Question #20
I = (19700 x 125%) / 240 = 102.6amps - 2awg
228 RW
Question #5
Ungrounded
404.2(A)
228.1
Question #3
Any Of These
400.14
228.2
Question #18
Front to back, top to bottom, & left to right
408.3 (E)(1)
228.3
Question #20
20'
410.30 (B)(1) ex 2
228.4
Question #7
18 - 36
422.16 (B)(1)(1)
228 RW
Question #2
4' above the floor operating on 24v
410.150 (C) (8)
228.1
Question #11
18 AWG
400.16
228.2
Question #16
6'7"
404.8(A)
228.3
Question #17
0"
410.16(A)(1) & (2)
228.4
Question #16
R=E^2 /P - (240^2) / 15000 =3.84ohms
I=E/R - 240/3.84 = 62.5amps
62.5a x 125% = 78.125a
100a Safety Switch