NEC article covering liquid tight flexible conduit
What is article 350
Fitting that does not require support per the NEC
What is a conduit body
Cubic inch space requirement for #12 conductor installed in a box or conduit fitting
What is 2.25
What is the most used conductor temperature rating used for determining conductor ampacity
What is 75 degree C
3" on an 1/8" scale drawing
What is 24'
Where you find all the circuit number for a specific branch circuit.
What is a panel schedule
Fitting used to prevent flammable vapors from entering a panel
What is a seal off.
What is conduit bodies are not required to be supported.
Insulation code for cross-linked polyethylene
What is X
Type of MC cable that may be direct buried
What is PVC coated
Diagram showing all panels and transformers and how and where are connected
What is a one line diagram
Shows a simplified view of the entire electrical distribution system
What is a one line diagram
Type of conduit fitting used to connect conduit to an enclosure in a wet environment
What is a threaded weatherproof hub.
Wireways, raceways and cables trays are all covered under this NEC chapter.
What is Chapter 3
Type of cable that uses semi conducting tape in its construction
What is high voltage cable
two tables that gives the allowable ampacity for insulated conductors in wireways and gutters
What is 310.16 and 310.18.
Place to find the complete part number for a particular light fixture
What is a fixture schedule
A 1/4" scale floor plan measurement of 16.25"
What is 65'
NEC section that requires separation of cables installed in a cable tray
What is section 392.80
Type of fastener used to attach permanent nameplates to motors or other electrical equipment
What is a drive screw
NEC article that covers the temperature rating of conductors
What is Article 310
Ampacity of #2, 75 degree insulated cable run in free air
What is 170 amps
What do these two line styles represent
_________ - - - - - - -
What wiring concealed is wall / ceiling and wiring exposed.
A sheet designation of S-4 will typically show this.
What is structural information
NEC section requiring the use of bonding bushings for concentric knockouts at service equipment
What is section 250.92
Maximum distance between supports for 1" PVC conduit.
What is 3'
Correction factor for 75 degree cable installed in a 150 degree ambient.
What is .38
Number of stands in 350 kcmil cable
What is 37 strands
What information is found on electrical floor plans
Location of outlets, switches, light fixtures and panels
What do clouded areas on plans represent
What are revisions