K for AL
What is 21.1
K for CU
What is 12.9
VA rating for a small appliance circuit.
What is 1500 VA
Load rating for a residential dryer.
What is 5000 VA or nameplate VA which ever is greater.
AWG Size Range
What is #40 - #4/0
208v, 1ph - 26.5a - #10 str - 145'
What is 9.3v
120v - 18a - #10 sld - 105'
What is 4.5v
Load for a general use receptacle for a continuous load
What is 225 VA
Demand load for one household dryer with a nameplate rating of 6 KW.
What is 6 KW
Ratio between square mils and circular mils
What is 0.7854
120v - 14.5a - #12 sld - < or > 3%
What is greater than 3%
These wire types typically have different resistances even for the same wire size.
What is solid and stranded
Correction factor for TW cable in a 40 deg C ambient.
What is .82
Min conductor rating for a tap over ten feet but less than 25 feet.
What is one third the rating of that conductor being tapped.
1 mil is equal to _______ inches.
What is 1/1000 inch
A sign load cannot exceed this.
What is 80%
Load rating for two residential cooking appliances rated 8.4 KW and 10.5 KW
10.8 KW
NEC Section that says that utilization equipment fastened in place shall not exceed 50% of the circuit load on a 15 or 20 amp branch circuit.
What is 210.23(2)
Load calculation for show window lights.
200va per linear foot times 1.25
400 POINTS!!!
400 POINTS
Although it may affect the percentage of voltage drop, this variable does not affect the actual voltage drop.
What is the circuit voltage
Min CMIL required for a 250' circuit to a 480/277v, 225a panel with a load of 175 amps of load.
What is 101,823
For resistance welder circuits, the rating of the overcurrent device cannot exceed what percentage of the welder nameplate current rating.
What is 300%
Number of receptacles required for a show window of 67'
What is 6 receptacles
Uninsulated wire available in both solid and stranded with various tempers.
What is red copper.