OHMS LAW+
100

total continuous load that can be connected to a 70A fuse

70 x .80=56A

100

derating factor & amperage per conductor for 8 current carrying #8 THHN conductors in a raceway?

70%, 55 x .70=38.5A

100

total overcurrent for a 35A 277v continuous load circuit

43.75A / 45A

100

How many receptacles SHOULD be connected to a 15A residential

15A x 120 x .80 / 180 = 8

100

what is the full load current for a 208 v 1∅ 5hp motor?

21A x 1.25 = 26.25A, #10 THWN

100

Volt Amps for a 1∅ 50A. 277V Circuit

13,850 VA or 13.85 kVA (A x V)

200

What size XHHW copper conductor would be use to supply a 52A continuous load in an ambient temperature of 38°C?

52A x 1.25 x .91 =59.15, #6 XHHW

200

How many VA and 20A 120v circuits are required to feed 15’ of simultaneously used heavy duty multi-outlet assembly?

15’ x 180 = 2,700 VA , 20*120v=2,400 , 2700/2400=1.12 (2 ckts)

200

how many heavy duty lamp holder can be connected to a 30A 120v circuit ?

30 x 120 = 3600 / 600 = 6

200

how many receptacles CAN be connected to a 15A residential circuit?

15A x 120 = 1800 VA / 180 =10

200

What size conductors would be used for a A/C with a nameplate rating of 35A 220v 1∅?

35 X 1.25=43.75A =#6 AWG

200

Volt amps for a 3∅ 225A 480V Circuit

187,056 or 187.056 kVA (AxVx1.732)

300

What is the voltage drop for a 50A, 480V, 3∅ circuit, 340’ long

1.732x340x.491x50/1000=14.45v

300

what is the total demand (kW) for an electric range rated at 13.5kW?

13.5kW - 12kW = 1.5 8 x .05=.4 x 1.5=.6 + 8 = 8.6

300

How many 200W continuous duty lamps can be connected to a 20A 120V circuit?

200x 1.25=250, 2400/250=9.6 (9 total)

300

What is the total VA required for a residence with 4 kitchens?

(2 x 1500VA x 4= 12000VA)

300

What size THWN conductors would be used for a 460v 3∅ 15hp motor design letter B ?

21A x 1.25 = 26.25A, #10 THWN

300

What is the total amperage of a load with a nameplate rating of 3∅ 480V 3750w?

3750/480X 1.732=13.53A

400

what is the total voltage drop for a single phase 277V circuit using 100A aluminum conductors, 220’ long?

2x 220’x21.2x100/105600=8.83v

400

what is the total demand kVA for 4 commercial ovens rated at 5kW 208 3∅ each?

5000 x 4 = 20,000 x .80 x 1.732 =27.7 kVA.

400

what is the overall recommended percentage for a branch circuit?

3%

400

What is the total VA required for a residence with 4 laundry rooms?

4 x 1500VA = 6000VA

400

What size non- time delay fuse would be used for a continuous 460v 3∅ 7.5 hp motor design letter E?            

11A x 1.25 x 3 = 41.25A, 45A fuse

400

What is the total circuit ampacity of a 6.75 kW load on a 1∅ 220V?

6.75x1000=6750/220=30.68A

500

How many VA and 20A 120v circuits are required to feed 75’ of show window?

200 x 75=15000 x 1.25= 18,750/ 2400=7.81(8-20a ckts)

500

What size THHN conductors and overcurrent would be required for a 120-gallon water heater rated at 8,500w at 240V?

8500 /240V = 35.41*1.25=44.27A (#8 THHN / 45A)

500

 total amp rating for a commercial 277v circuit with 1x light fixture at 1500W and 2 x 3.5A lights that are on for 9 hours a day?

(1500/277=5.41A, 3.5 x2=7, 5.41 + 7x 1.25 = 15.5 A)

500

what is the total demand VA for 6 residential dryers rated at 4875va each?  

5000 x 6 x .75=22,500VA

500

What size THHW copper conductor  and circuit breaker would be required to supply a resistance welder with a nameplate rating of  65A with a 70% duty cycle?

65 x .86 = 55.9, #4 THHW, 55.9x 300% = 167.7A , 175A breaker

500

total overcurrent size for a 120v circuit with a non-continuous load of 15A and 2x 2.5A continuous loads?

2.5x2x 1.25 +15=21.25=25A