Yellow Background with Black Lettering
What are the colors for Medical Air Labeling?
The standard Operating Pressure for Nitrogen
What is 160-185 psi?
O2
What is Oxygen?
-22 degrees Fahrenheit
What dew point does Instrument Air alarm at?
3'
What is the clearance around the EOSC?
Blue Background with White Lettering
What are the Nitrous Oxide colors for labeling?
The Standard operating pressure for Oxygen
What is 50-55 psi?
Med Air
What is Medical Air?
The temperature that cylinders in use shall be prevented from reaching
What is 125 degrees Fahrenheit?
The distance a medical air intake shall be located from vents, exhausts etc.
What is 25 Feet?
Black Background with White lettering
What are the Nitrogen colors for labeling?
The Standard operating pressure for Instrument Air
What is 160-185 psi?
The abbreviated name for Nitrogen
What is N2?
The temperature Cylinders for Nitrous Oxide shall never be lower than
What is 20 degrees Fahrenheit?
10 feet
What is the distance a medical air intake shall be located from windows, doors or openings in the building?
Gray Background with black lettering
What are the Carbon Dioxide colors for labeling?
160-185 PSI
What is the standard operating pressure for Support Gases?
The Abbreviated name for Carbon Dioxide
What is CO2
130 degrees Fahrenheit
What is the maximum temperature of ambient air around medical gas piping?
ASSE 6010
What is the professional qualification standard for Med gas Installers?
Red Background with White lettering
What are the instrument air colors for labeling?
The Standard operating pressure for Carbon Dioxide
What is 50-55 PSI?
N2O
What is Nitrous Oxide?
32 degrees Fahrenheit
What is the maximum dew point for Medical Air?
The professional qualification standard of med gas verifiers
What is ASSE 6030?