A
B
C
D
E
100

The cooling of generator loads is the purpose of what system?

TACW System

100

What is the purpose of the Main feedwater system?

Provide continuous flow of water at a uniform temperature to all steam generators under normal operating conditions.

100

What RPM does the turning gear turn the MFPT in each unit

Unit 1 - 4 RPM

Unit 2 - 104 RPM

100

What is the cooling water for the containment chill water system?

NESW

100
What provides 250 VDC to TDAFP and AMSAC inverters

N train battery/charger

200

What is the relationship between TACW and Condensate?

Provides make up water

Provides cooling in open loop

200

Emergency leak off valves open and modulate to ensure minimum flow of how many gallons of water?

4,000 gpm

200

What is the normal operating steam for the MFP 

Low pressure stream from the MSR

200
The condensate system starts and ends and what components?

Hotwell to Main Feed Pumps

200

There is 87 PSI on the control air header pressure. How many and what compressors are on.

Both plant air compressors.

Both CAC's

300

Seal Air for the compressor needs to be greater than what PSI

16
300

How long can you cool the reactor with a CST level of 182,000 gallons. 

9 hours


300

This is design feature to minimize the risk of fully draining a lube oil tank during operation.

Loop Seal

300

Define the purpose of the High Voltage Distribution System?

Ensures a continuous supply of electrical power to all essential plant equipment during normal operation and under abnormal conditions

300

The measurement of relative clarity of a liquid is called what?

Turbidity

400

TACW heat exchanger cooling in closed loop is provided by?

Circulating Water

400

Main Feed Pump trips at what percentage of overspeed on IOPS

>110% overspeed

400

How many lube oil pumps doe the MFP have?

3 - Shaft, AC, DC

400

Unit 1 TDAFP has drained the CST, what is the back up suction supply?

ESW

400

CRV-224 modulates open with a feed pump suction psi under

240 psig

500

Unit 2 TACW East pump is running, and West is in standby. At what set point will the west autostart.

145 psig

500

What valve do you manipulate to by-pass a string of HP feedwater heaters?

FMO-260

500

Condensate Booster pump is out of service, what is the back up which provides MFP seal water.

Main Feed Pump Seal Water Pump

500

The unit 1 East ESW pump is powered from what

T11D

500

Main feedpump trips on lowering suction pressure of what psi for what duration

less than 180 psi for 5 seconds